InteliMains 210 Global Guide
524
Other type
Alarm Type
BOR
Alarmlist message
BOR + Name of analog input
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
This alarm indicates that the value of general analog protection is out of BOR
protection limit.
BOR AIN Prot
back to List of alarms level 2
Alarm Type
BOR
Alarmlist message
BOR + Name of binary input
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
Binary input also can be adjusted like alarm. In this case message in alarmlist
contains prefix - BOR and binary input name. This alarm occurs, when appropriate
binary input is active.
BOR BIN Protection
back to List of alarms level 2
Alarm Type
BOR
Alarmlist message
BOR Current Unbalance
Alarm evaluated
All the time
Related applications
MCB, MGCB, BTB
Description
This alarm evaluates the unbalance of the phase currents, i.e. the difference
between highest and lowest phase current at any given time. The following
setpoints are related to it:
adjusts the maximum allowed difference
between the highest and lowest phase current at any given time.
Current Unbalance Delay (page 188)
adjusts the alarm delay.
Current Unbalance
back to List of alarms level 2
Alarm Type
BOR
Alarmlist message
BOR Overcurrent IDMT
Alarm evaluated
All the time
BOR Overcurrent IDMT