InteliMains 210 Global Guide
201
Setpoint group
Power Management
Related FW
2.0.0
Range [units]
0 .. 3 600 [s]
Default value
10 s
Alternative config
NO
Step
[s]
Comm object
10795
Related applications
MCB, MGCB
Description
This setpoint is used for adjusting the delay of changing the power band if the load demand drops below the
lower limit of the current power band. Setpoint is taken into account only if
#Priority Auto Swap (page 192)
=
Efficient.
#Power Band Change Down Delay
Subgroup: Group Settings
Setpoint group
Power Management
Related FW
2.0.0
Range [units]
1,2 .. 32 [-]
Default value
1 s
Alternative config
NO
Step
1 s
Comm object
10589
Related applications
MCB, MGCB
Description
This setpoint selects the control group (to get more information on this function please refer to the chapter
to which the particular gen-set belongs. If there aren't logical groups at the site,
adjust the setpoint to 1.
Note:
This function is not supported in BTB application.
Control Group
Setpoint group
Power Management
Related FW
2.0.0
Range [units]
1,2 .. 32 [-]
Default value
1 s
Alternative config
NO
Step
1 s
Comm object
10590
Related applications
MCB, MGCB
Description
If the input
of this particular controller is used to provide the "group link" information
for two Control groups (to get more information refer to the chapter
), then this
setpoint is used to select which group is located at the left side of the group link breaker (bus tie breaker). If
this particular controller is not used for the group link function, adjust this setpoint to 1.
Group Link L