InteliMains 210 Global Guide
200
Subgroup: Run Hours Equalization
Setpoint group
Power Management
Related FW
2.0.0
Range [units]
0 .. 65 000 [h]
Default value
100 h
Alternative config
NO
Step
1 h
Comm object
9919
Related applications
MCB, MGCB
Description
This setpoint adjusts the "dead-band" for the running hours equalization function (
= Run Hours Equal). The priorities are swapped not until the relative engine hours difference is higher
than this dead-band.
#Run Hours Max Difference
Setpoint group
Power Management
Related FW
2.0.0
Range [units]
0,0 .. 200000,0 [h]
Default value
0,0 h
Alternative config
NO
Step
0,1 h
Comm object
10600
Related applications
MINT
Description
Running hours base corrects actual Running hours differences between particular gen-sets.
Example:
Gen-set 1 actual Running hours = 1000 h.
Gen-set 2 actual Running hours = 2000 h.
Adjust this setpoint for Gen-set 1 = 1000 h and for Gen-set 2 = 2000 h to be on the same base for
Running Hours Equalization.
Note:
This function is not supported in BTB application.
Run Hours Base
Subgroup: Efficient Mode
Setpoint group
Power Management
Related FW
2.0.0
Range [units]
0 .. 3 600 [s]
Default value
10 s
Alternative config
NO
Step
[s]
Comm object
8896
Related applications
MCB, MGCB
Description
This setpoint is used for adjusting the delay of changing the power band if the load demand rose above the
upper limit of the current power band. Setpoint is taken into account only if
#Priority Auto Swap (page 192)
=
Efficient.
#Power Band Change Up Delay