InteliMains 210 Global Guide
194
Setpoint group
Power Management
Related FW
2.0.0
Range [units]
#Starting Load Reserve 1 (page 193)
.. 32 000 [kW]
Default value
110 kW
Alternative config
NO
Step
1 kW
Comm object
8491
Related applications
MCB, MGCB
Description
This setpoint is used to adjust the load reserve for stop of next gen-set in absolute mode. i.e.
= ABS.
IMPORTANT: Logical binary input
has to be deactivated,
otherwise setpoints of Load Reserve Set 2 are used.
Note:
See
chapter for more information.
#Stopping Load Reserve 1
Setpoint group
Power Management
Related FW
2.0.0
Range [units]
0 ..
#Stopping Rel Load Reserve 1 (page 195)
[%]
Default value
60 %
Alternative config
NO
Step
1 %
Comm object
10648
Related applications
MCB, MGCB
Description
This setpoint is used to adjust the load reserve for start of next gen-set in relative mode. i.e.
= REL.
IMPORTANT: Logical binary input
has to be deactivated,
otherwise setpoints of Load Reserve Set 2 are used.
Note:
See
chapter for more information.
#Starting Rel Load Reserve 1