InteliLite Global Guide
84
5.4.4 Interconnection variants
RS232
It is necessary to use CM-RS232-485 communication module on both Master controller and Remote display.
COM 1 communication channel is used with these settings:
COM 1 Mode: Direct
COM 1 Communication Speed: 57600 or 115200 bps
Controller Address: 1 – 32
The maximal distance between Master controller and Remote display is 10 m for RS-232 connection. It is
recommended to use standard Null modem cable (crossover cable), although three wires (TxD, RxD, GND)
RS-232 connection is enough for communication.
RS485
It is necessary to use CM-RS232-485 communication module on both Master controller and Remote display.
COM 2 communication channel is used with these settings:
COM 2 Mode: Direct
COM 2 Communication Speed: 57600 or 115200 bps
Controller Address: 1 – 32
The maximal distance between Master controller and Remote display is 1200 m for RS-485 connection. It is
recommended to use shielded twisted-pair cables that comply with the EIA RS-485 standard to reduce
interference and to achieve maximal distance.
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...