InteliLite Global Guide
599
Image 8.188 Stop Solenoid 2
Note:
If
Additional running engine indications (page 117)
went off during 5 s pause than Stop
Solenoid is not activated again otherwise stop solenoid is activated again.
Logical binary outputs alphabetically (page 539)
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
1249
Description
The binary output depends on measured generator active power. Power is compared with generator nominal
active power with use of hysteresis and with delay of switch 1 s.
When the measured active power is equal to or bigger than 5 % of
for 1 s then
the binary output is closed.
When the measured active power is equal to or lower than 3 % of
for 1 s then
the binary output is opened.
Supplying Load
back to Logical binary outputs alphabetically
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
1997
Description
This logical binary output is result of internal comparator which compares statistic values
and
. Binary output is active when
are
equal or higher than the
Swap Start
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...