InteliLite Global Guide
48
4.4.13 Analog as binary or tristate inputs
Analog inputs can be used also as binary or tri-state, i.e. for contact sensors without or with circuit check. The
threshold level is 750 Ω. In the case of tri-state, values lower than 10 Ω and values over 2400 Ω are evaluated as
sensor failure (short or open circuit).
Image 4.29 Analog inputs as tristate
Image 4.30 Analog inputs as binary
Note:
The name, sensor characteristic and alarm types for each analog input have to be assigned during
configuration.
Note:
Tristate and binary sensors are not suitable for Analog Switch functions.
4.5 Plug-in module installation
4.5.1 Installation
Remove the back cover. To do this, press four holders which are located in corners.