InteliLite Global Guide
319
Setpoint group
Scheduler
Related FW
1.9.0
Range [units]
Disabled / 1..
[h]
Default value
Disabled
Alternative config
NO
Step
1 h
Comm object
14332
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Conditioned by the setpoint
Description
Alarm
comes up after xx running hours from adjusting the
. Hours are adjusted by this setpoint.
Image 8.61 Rental Timer 1 Wrn
Rental Timer 1 Wrn
Setpoint group
Scheduler
Related FW
1.9.0
Range [units]
[DD/MM/YYYY]
Default value
01/01/2015
Alternative config
NO
Step
1 day
Comm object
14367
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Another engine start is not allowed when this timer elapsed. This timer is based on date. At the midnight of
the last day the alarm
Rental Timer 2 Elapsed (page 654)
will be recorded in alarm list and the binary
output
will close.
IMPORTANT: To reset
we have to set up
again. It means go to setpoint group Scheduler and to the setpoint
.
Then press enter button
, change the value if it is necessary and press enter button
again.
IMPORTANT: To disable
set date to 01/01/2015.
Rental Timer 2
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...