InteliLite Global Guide
231
Setpoint group
Generator settings
Related FW
1.9.0
Range [units]
Generator Undervoltage Wrn (page 232)
..
Generator Overvoltage Sd (page 230)
[%]
Default value
110 %
Alternative config
NO
Step
1 % of
Nominal Voltage Ph-N (page 179)
or
Nominal Voltage Ph-Ph (page 179)
Comm object
9686
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator overvoltage protection. All three phases are checked. Maximum out of three is used.
Note:
Phase to phase and phase to neutral voltages are used for this protection.
Generator Overvoltage Wrn
Setpoint group
Generator settings
Related FW
1.9.0
Range [units]
0 ..
Generator Undervoltage Wrn (page 232)
[%]
Default value
70 %
Alternative config
NO
Step
1 % of
Nominal Voltage Ph-N (page 179)
or
Nominal Voltage Ph-Ph (page 179)
Comm object
8293
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator undervoltage protection. All three phases are checked. Minimum out of three is used.
Note:
Phase to phase and phase to neutral voltages are used for this protection.
Note:
When there is no control of breakers, the type of protection is Sd not BOC.
Generator Undervoltage BOC
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...