InteliLite Global Guide
223
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0 ... 1 000 [-]
Default value
1
Alternative config
NO
Step
1
Comm object
10995
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Only if LBI
is configured
Description
This setpoint adjusts the rate of increasing of the Pulse Counter 2 function. The module counts pulses at the
input
and if the input pulses counter reaches value given by this setpoint, the
counter value
is increased by 0,1 and input pulses counter is reset to 0. Both
counter value and input pulses counter are stored in the nonvolatile memory.
Conversion Coefficient Pulse 2
Subgroup: Power switch
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0 .. 32 000 [kW]
Default value
100 kW
Alternative config
NO
Step
1 kW
Comm object
11658
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Visible only if the logical binary output
is configured.
Description
Threshold level for switching the binary output
on.
Image 8.15 Power Switch Level On < Level Off
Power Switch On
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...