InteliLite Global Guide
221
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
Battery Undervoltage (page 220)
.. 40,0 [V]
Default value
36,0 V
Alternative config
NO
Step
0,1 V
Comm object
9587
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Warning threshold for high battery voltage.
Battery Overvoltage
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0 .. 600 [s]
Default value
5 s
Alternative config
NO
Step
1 s
Comm object
8383
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Delay for
Battery Undervoltage (page 220)
and
Battery Overvoltage (page 221)
protection.
Battery <> Voltage Delay
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0 .. 15 [min]
Default value
5 min
Alternative config
NO
Step
1 min
Comm object
11374
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Conditioned with LBI
Description
Delay for LBI
Battery Charger Fail Delay
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...