InteliLite Global Guide
217
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0 .. 600 [s]
Default value
5 s
Alternative config
NO
Step
s
Comm object
14683
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
When the value of fuel drop per hour is higher than
this delay stars count
down. After count down of this delay alarm
is activated.
Maximal Fuel Drop Delay
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0 ..
[%]
Default value
20 %
Alternative config
NO
Step
1 %
Comm object
10100
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Visible only if the logical binary output
is configured and
logical binary input
isn’t configured
Description
Threshold level for switching the binary output
on.
Image 8.13 Fuel Pump On
IMPORTANT: When binary input
is configured then binary
output
is control by this binary input. Setpoints Fuel Pump On and
are not evaluated!
Note:
Value from analog input has higher priority than ECU.
Note:
This setpoint is visible only if the logical binary output
is configured.
Fuel Pump On
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...