InteliLite Global Guide
194
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
-20,0 .. 80,0 [°C]
Default value
0,0 °C
Alternative config
NO
Step
0,1 °C
Comm object
15716
Related applications
MRS. AMF
Config level
Advanced
Setpoint visibility
Only when LBO
is configured and setpoint
= Temp Based.
Description
This setpoint adjust the base temperature for Choke function. When temperature will be higher than this
setpoint, Choke Time will be always 0. When temperature will be lower than this setpoint, Choke Time will
be calculated by curve adjusted via setpoint
. When setpoint
is set to
Fixed Time
value, setpoint
Choke Start Temp
has no effect.
Choke Start Temp
Summary of Contents for InteliLite AMF25
Page 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Page 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Page 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Page 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Page 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Page 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Page 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...