InteliLite4 AMF20 Global Guide
73
is still active) or is off (if no alarm is active).
MAINS
status indicator. There are two states – Mains OK (indicator is green) and Mains
failure (indicator is red). Green LED is on, if mains is present and within limits. Red LED
starts blinking when the mains failure is detected and after the Gen-set has started and
connected to the load it lights permanently until the mains failure disappears.
Graphic B/W display, 132 × 64 px.
GCB Status
. Consists of 3 green LEDs. The middle green LED is on if GCB is closed. It
is driven by GCB CLOSE/OPEN output or by GCB feedback signal. Side green LEDs are
on in case the generator status indicator is ok.
LOAD
. Green LED is ON if load is supplied by mains or by generator. It means, that Gen-
set or mains is OK and proper circuit breaker is closed.
MCB Status
.Consists of 3 green LEDs. The middle green LED is on if MCB is closed. It is
driven by MCB CLOSE/OPEN output or by MCB feedback signal. Side green LEDs are
on in case the mains status indicator is ok.
5.3.2 Display screens and pages structure
The displayed information is structured into "pages" and "screens". Use the PAGE button to switch over the
pages.
The page Measurement consists of screens which display measured values such as voltages, current, oil
pressure etc.; computed values such as Gen-set power, statistic data and the alarm list on the last screen.
The page setpoints contains all setpoints organized to groups and also a special group for entering a
password.
The page History log shows the history log with the most recent record displayed first.
Main Screen
Symbols
Padlock – active when LBI A
CCESS
L
OCK
is active
R – active when there is active remote connection to controller
Exclamation mark – active when there is any alarm in alarm list