InteliLite4 AMF20 Global Guide
562
The alarm will be also issued if the breaker does not respond to an open
or close command within 5 seconds.
back to List of alarms level 2
Alarm Type
SD
Alarmlist message
Sd Generator L1 > Voltage
Alarm evaluated
Generator excited only
Related applications
AMF, MRS
Description
This alarm evaluates the generator phase voltage in phase 1. The following
setpoints are related to it:
Generator Overvoltage Sd (page 264)
Generator <> Voltage Delay (page 266)
Sd Generator L1 Overvoltage
back to List of alarms level 2
Alarm Type
SD
Alarmlist message
Sd Generator L2 > Voltage
Alarm evaluated
Generator excited only
Related applications
AMF, MRS
Description
This alarm evaluates the generator phase voltage in phase 2. The following
setpoints are related to it:
Generator Overvoltage Sd (page 264)
Generator <> Voltage Delay (page 266)
Sd Generator L2 Overvoltage
back to List of alarms level 2
Alarm Type
SD
Alarmlist message
Sd Generator L3 > Voltage
Alarm evaluated
Generator excited only
Related applications
AMF, MRS
Description
This alarm evaluates the generator phase voltage in phase 3. The following
setpoints are related to it:
Generator Overvoltage Sd (page 264)
Generator <> Voltage Delay (page 266)
Sd Generator L3 Overvoltage
back to List of alarms level 2
Alarm Type
SD
Alarmlist message
Sd Generator L1L2 > Voltage
Alarm evaluated
Generator excited only
Related applications
AMF, MRS
Description
This alarm evaluates the generator phase to phase voltage between phases 1
Sd Generator L1L2 Overvoltage