InteliLite4 AMF20 Global Guide
481
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
43
Description
The output is intended for control of open coil of generator circuit breaker. The output gives a pulse in the
moment the breaker has to be opened. The pulse lasts until the feedback deactivates, but at least for 5
seconds.
Image 8.37 GCB OFF Coil command
GCB OFF Coil