InteliLite4 AMF20 Global Guide
457
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
620
Description
The controller is switched to the AUTO mode (there are four modes OFF / MAN / AUTO / TEST) when this
binary input is active. When opens controller is switched back to previous mode.
This binary input has the lowest priority from Remote OFF / MAN / AUTO / TEST binary inputs
Remote control priority:
Remote OFF (Highest priority)
Remote TEST
Remote MAN
Remote AUTO (Lowest Priority)
Remote AUTO
back to Logical binary inputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
4
Description
If the input is active, the controller will not accept any actions regarding the system control – e.g. writing of
commands and setpoint changes via remote communication interfaces.
Remote Ctrl Lock
back to Logical binary inputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
618
Description
The controller is switched to the MAN mode (there are four modes OFF / MAN / AUTO / TEST) when this
binary input is active. When opens controller is switched back to previous mode.
Remote control priority:
Remote OFF (Highest priority)
Remote TEST
Remote MAN
Remote AUTO (Lowest Priority)
Remote MAN