InteliLite4 AMF20 Global Guide
332
Subgroup: COM2 Setting
COM2 Mode
Setpoint group
CM-RS232-485
Related FW
1.3.0
Range [units]
Direct / MODBUS / DualSlave / Dual Master [-]
Default value
Direct
Alternative config
NO
Step
[-]
Comm object
24451
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Only if relevant module is installed
Description
Communication protocol switch for the COM2 channel.
Direct
InteliConfig communication protocol via serial cable.
MODBUS
MODBUS protocol.
DualSlave
Dual operation protocol – slave function
DualMaster
Dual operation protocol – master function
COM2 Communication Speed
Setpoint group
CM-RS232-485
Related FW
1.3.0
Range [units]
9600 / 19200 / 38400 / 57600 / 115200[bps]
Default value
57600 bps
Alternative config
NO
Step
[-]
Comm object
24340
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Only if relevant module is ins conditioned by the setpoint
Description
If the direct mode is selected on COM2 channel, the direct communication speed of controller part of line
can be adjusted here. Speed of second part of line has to be adjusted to the same value.