InteliLite4 AMF20 Global Guide
277
Mains Voltage Unbalance Delay
Setpoint group
Mains Settings
Related FW
1.3.0
Range [units]
0.0 .. 600.0 [s]
Default value
2.0 s
Alternative config
NO
Step
0.1 s
Comm object
8447
Related applications
AMF
Config level
Advanced
Setpoint visibility
Conditioned by the setpoint
Default Application Select (page 217)
Description
Delay for
Mains Voltage Unbalance (page 276)
protection.
Subgroup: Mains Frequency Limits
Mains Overfrequency
Setpoint group
Mains Settings
Related FW
1.3.0
Range [units]
Mains Underfrequency (page 279)
.. 150 [%]
Default value
102.0 %
Alternative config
NO
Step
1.0 % of
Comm object
8310
Related applications
AMF
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Default Application Select (page 217)
Description
Threshold for Mains overfrequency.