InteliLite4 AMF20 Global Guide
276
Mains Overvoltage Delay
Setpoint group
Mains Settings
Related FW
1.3.0
Range [units]
0.0 .. 600.0 [s]
Default value
2.0 s
Alternative config
YES
Step
0.1 s
Comm object
8306
Related applications
AMF
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Default Application Select (page 217)
Description
Delay for
protection.
Mains Undervoltage Delay
Setpoint group
Mains Settings
Related FW
1.3.0
Range [units]
0.0 .. 600.0 [s]
Default value
2.0 s
Alternative config
YES
Step
0.1 s
Comm object
8308
Related applications
AMF
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Default Application Select (page 217)
Description
Delay for
protection.
Mains Voltage Unbalance
Setpoint group
Mains Settings
Related FW
1.3.0
Range [units]
1 .. 150 [%] of
Nominal Voltage Ph-Ph (page 211)
or
Default value
10 %
Alternative config
NO
Step
1 %
Comm object
8446
Related applications
AMF
Config level
Advanced
Setpoint visibility
Conditioned by the setpoint
Default Application Select (page 217)
Description
Threshold for Mains voltage unbalance.