InteliLite4 AMF20 Global Guide
250
Subgroup: Fuel Pump
Fuel Pump On
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
0 ..
[%]
Default value
20 %
Alternative config
YES
Step
1 %
Comm object
10100
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
All the time
Description
Threshold level for switching the binary output
on.
Image 8.13 Fuel Pump On
IMPORTANT: When binary input
is configured then binary
output
is control by this binary input. Setpoints Fuel Pump On and
are not evaluated!
Note:
Value from analog input has higher priority than ECU.