InteliLite4 AMF20 Global Guide
234
Choke Lead
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
0 .. Prestart Time [s]
Default value
0 s
Alternative config
NO
Step
1 s
Comm object
15774
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Only when LBO
is configured.
Description
This setpoint adjust the lead of logical binary output C
HOKE
.
is activated before logical
binary output
.
Note:
In case Choke Lead is longer than 8 s (cranking fail pause), Choke Lead will be limited to 8 s
(cranking fail pause time). This limitation is applied only for cranking fail pause, Choke Lead in Prestart
stays unchanged.