InteliLite4 AMF20 Global Guide
224
Screen Filter
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
Enable / Disabled [-]
Default value
Disabled
Alternative config
NO
Step
[-]
Comm object
15889
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Every analog value showed on CU screen is filtered when setpoint is enabled.
Group: Communication Settings
Subgroup: Controller Address
Controller Address
Setpoint group
Communication
Settings
Related FW
1.3.0
Range [units]
1 .. 32 [-]
Default value
1
Alternative config
NO
Step
1
Comm object
24537
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Controller identification number. It is possible to set controller address different from the default value (1)
so that more controllers can be interconnected (via RS485) and accessed e.g. from Modbus terminal.
Note:
When opening connection to the controller it's address has to correspond with the setting in PC
tool.