InteliLite4 AMF20 Global Guide
213
Nominal Voltage High Leg D
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
80 .. 20 000 [V]
Default value
277 V
Alternative config
YES
Step
1 V
Comm object
20813
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Visible if one of the three
Setpoints is set to
Autodetect.
Description
This setting is used as phase-neutral
Nominal Voltage Ph-N (page 211)
by the voltage autodetect
function, if detected
is High Leg D. Set this setpoint to 120 V with high leg
delta system, which works with the high leg voltage 208 V (L2-N).
Nominal Voltage SplitPhase
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
80 .. 20 000 [V]
Default value
120 V
Alternative config
YES
Step
1 V
Comm object
20814
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Visible if one of the three
Setpoints is set to
Autodetect.
Description
This setting is used as phase-neutral
Nominal Voltage Ph-N (page 211)
by the voltage autodetect
function, if detected
is SplPhL1L2 or SplPhL1L3.