InteliLite4 AMF20 Global Guide
208
Gen CT Ratio Prim
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
1 .. 10000 [A]
Default value
2000 A
Alternative config
NO
Step
1 A
Comm object
8274
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Current transformers ratio of Gen-set.
Gen CT Ratio Sec
Setpoint group
Basic settings
Related FW
1.3.0
Range [units]
- [/1A / /5A]
Default value
/5A
Alternative config
NO
Step
-
Comm object
10556
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Current transformers ratio of Gen-set.