ID-Mobile Global Guide
161
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
157
Description
Engine “edge sensitive” stop request. The first edge changes engine state from running to cooling. REMOTE
STOP signal is equivalent to external terminal Stop button.
Note:
Binary inputs Remote start, Remote stop are edge (not level) sensitive. Minimal pulse duration to
safely detect the edge is at least the 120 ms (binary input sampling rate is 100 ms).
The second Remote Stop edge skip the (rest of) cooling.
Remote Stop
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
628
Description
Active input switches (by rising edge)
to Modbus (from other like STANDARD,
ECU LINK).
RS485 Mode Mod
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
212
Description
Active input switches (by rising edge)
to STANDARD (from other like Modbus,
ECU LINK).
RS485 Mode Std
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
46
Description
Binary input can be used for engine running indication e.g. via Oil pressure contact. Active Running
indication blocks engine start (to avoid starter damage).
Engine running state =
RPM >
or
>
or
Active Binary input Run indication1 or
Active Binary input Run indication2 or
Active Binary input Run indication3 (
) or
>
StartPCoolant (AS only) (page 78)
RunIndication1