InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf,
©ComAp – August 2015
79
Default value: 5s
7.4.6 CrnkFail pause
[s]
Pause between crank (engine start) attempts.
Step:
1s
Range:
5 - 60s
Default value: 8s
7.4.7 Crank attempts
[-]
Maximum number of crank (engine start) attempts.
Step:
1
Range:
1 - 10
Default value: 3
7.4.8 Idle time
[s]
Idle time delay starts when RPM exceeds
Start RPM
. Start fail is detected when during Idle state RPM
decreases below 2.
During the
Idle time
timer running the binary output IDLE/NOMINAL is opened, when it expires the
IDLE/NOMINAL output closes. Binary output IDLE/NOMINAL opens during Cooling period again.
Note:
Engine can be switched between Idle and Running state by Binary input Nominal/Idle in MAN mode.
Step:
1s
Range:
0 - 600s
Default value: 12s
7.4.9 Idle speed
[RPM]
Speed request in engine Idle state i.e. after engine start or when switched to Idle in MAN mode by
Binary input Nominal/Idle and after Engine ShutDown.
Step:
1RPM
Range:
Starting RPM
–
MinSpeedLimit
Default value: 800RPM