InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf,
©ComAp – August 2015
74
H
INT
When LBI Nominal/Idle is configured (to a physical binary input), it has priority and the
switching between the nominal and the idle speed by I/0 button is blocked.
Conveyor:
Initial condition: Running engine. Press I/0 button activates BO
Horn
. After the horn
signal, the BO
Conveyor
is activated.
RegReqst:
Switches between setpoints
Request 1
and
Request 2
as requested value input for
regulator.
R RegDis:
In AUT mode, switching the I/0 button allows or disable the PI regulation to work.
When the regulation is blocked, the regulator analog output is set according to the
constant
Regulator
:
Reg bias
.
CloseLoad:
When the engine is in the status Ready to Load, this option switches ON and OFF the
LBO
Close Load
. When the engine is not in the status Ready to Load, the button has
no influence.
N
OTE
:
The applications without the information about the speed can not reach the status
Ready to Load and therefore, the load can not be switched by the I/O button.
That’s
why, in the case of settings: SP
Gear teeth
= 0, SP
RPM source
= PickUp, no ECU,
the condition sufficient for LBO
Close Load
activating by the I/O button is the Running
state.
Toggle:
Switches ON and OFF the LBO
Toggle
, no other consequences.
7.2.11 RunHoursSource
[ECU, INTERNAL, AUTO]
This setpoint is used for adjustment of RunHours source of the engine.
ECU:
RunHours are all the time read from ECU.
INTERNAL:
RunHours are counted from the inner counter of the controller.
AUTO:
If is coming from ECU rational value higher than 0, then the RunHours are taken from
ECU, in second case are displayed internal hours from controller. Default state.
C
AUTION
!
Some types of ECUs reset RunHours counter to 0, if the supply was disconnected.
7.2.12 Main Screen
[SHOW TIMERS, SHOW AIN]
Change the display of the main Measurment screen.
SHOW TIMERS:
Standard display with timers on the left side of the screen. Default state.
SHOW AIN:
Instead of timers are on the left side of the screen displayed values of analog
inputs AIN6 and AIN7.
7.3 Comms Settings
7.3.1 ControllerAddr
[-]
It is controller
’s identification number. It is possible to set controller address different from the default
value 1 so that more InteliDrive Lite controllers can be interconnected (via RS485) and accessed e.g.
from Modbus terminal.
Adresses:
1 - 32