9.3.22 Conveyor
Initial condition: Running engine.
Rising edge BI Conveyor activates BO Horn for
Engine params
:
Conveyor horn.
And after horn is
over activates the BO Conveyor.
The second rising edge of BI Conveyor opens the BO Conveyor. BO Conveyor is deactivated in case
of Sd protection.
BI Conveyor
BO Conveyor
BO Horn
9.3.23 LoadRequest2
Active input switches the Load limit request to
Load limit
:
LoadRequest2
setpoint.
9.3.24 LoadRegDisable
Active input disables the Load limit PI loop and switches analog output to constant
Load limit
:
Load
bias
.
9.3.25 RegRequest2
Active input switches the Regulator limit request to
Regulator
:
Request2
setpoint.
9.3.26 R Reg Disable
Active input disables the Regulator PI loop and switches analog output to constant
Regulator
: Reg
bias
.
9.3.27 Clear DayCons
DayCons is the counter which cumulates the instantanous consumption coming from ECU. It shows
the total consumption since the counter reset. Counte reset happen at the midnight of the controller
clocks. LBI Clear DayCons resets the counter DayCons.
H
INT
The function works when the controller is connected to an ECU or in other case is consumption
counted from the changes of analog input value Fuel rate and setpoint
Engine params:
FuelTankVolume.
9.3.28 Clear TripCons
TripCon is the counter which cumulates the instantanous consumption coming from ECU. It shows the
total consuption since last reset by LBI Clear TripCon. This LBI resets the counter TripCons.
H
INT
The function works when the controller is connected to an ECU or in other case is consumption
counted from the changes of analog input value Fuel rate and setpoint
Engine params:
FuelTankVolume.