InteliDrive Lite, SW version 1.9
ID-FLX-Lite-1.9r1 Reference Guide.pdf,
©ComAp – August 2015
106
Step:
1s
Range:
0 - 3600s
Default:
0s
H
INT
The corresponding BIN protection has to be configured as Running only in LiteEdit.
7.7.73 DEF Level Min
[%]
Diesel Exhaust Fluid level protection activates LBO DEF Tank Level when received level (J1939 -
SCR - Selective Catalytic Reduction message) is below
DEF Level Min
for more than (fix) 3s delay.
This function is active for IVECO NEF&&Cursor engine. LBO can be active for running engine only.
Step:
1%
Range:
0 - 150%
Default:
10%
7.7.74 DEF Level Max
[%]
Diesel Exhaust Fluid level protection deactivates LBO DEF Tank Level when received level (J1939 -
SCR - Selective Catalytic Reduction message) is above
DEF Level Max
for more than (fix) 3s delay.
This function is active for IVECO NEF&&Cursor engine.
Step:
1%
Range:
0 - 150%
Default:
90%
N
OTE
:
DEF Level is usual signage of Urea tank level, which is more often used in United States.
7.8 Date/Time
7.8.1 Time stamp per
[min]
This setpoint is dedicated to adjustment of time interval for periodical history records.
Step:
1min
Range:
0 - 200min
Default:
60min
7.8.2 SummerTimeMod
[DISABLED,
WINTER,
SUMMER,
WINTER-S,
SUMMER-S]
DISABLED:
Automatic switching between summer and wintertime is disabled.
WINTER (SUMMER):
Automatic switching between summer and winter time is enabled and
it is set to winter (summer) season.
WINTER-S (SUMMER-S) :
Modification for southern hemisphere.