ID-FLX Lite Global Guide
61
5.15.7 Engine timer
MAN mode
Set the
. Start engine in MAN mode by START button. Engine stops itself after
Running Timer is over. The STOP button cancels timer (forces cooling), the second STOP cancels cooling
(forces engine stop). Engine stays running when Running Timer = 0.
AUT mode
Engine starts and runs all the time when the
is closed. Running Timer is activated
after Rem start/stop is opened. To stop the engine the Rem start/stop has to be opened or controller switched to
MAN. Panel STOP button has no effect when Rem start/stop is closed in AUT, but skip the timer and switch to
cooling when Rem start/stop is opened.
Note:
The controller also includes two identical timers with function for auto start and stop with different
condition. Use Date/Time setpoints group. For explanation
.
MAN mode
AUT mode
RunTimer = 0
= disabled
RunTimer > 0
= enabled
RunTimer
= 0
=
disabled
RunTimer > 0
= enabled
Rem s/s
= ON
No function
Start and Run unlimited time
Rem s/s
= OFF
Cooling
Cooling after RunTimer is
over
START
Engine runs unlimited
time until STOP
Engine start-runs Run time
and then CoolingStop
No
function
When Rem s/s = OFF only:
Engine start-runs Run.time
and then Cooling-Stop
STOP
Cooling
No function when Rem s/s = 1
Cancels timer when Rem s/s = 0
2nd
STOP
Stop
5.15.8 Protections
The controller protects the engine and the driven machine as well.
When an alarm occurs, these actions are taken: on the controller front side, the yellow or red LED starts to blink.
The LBO Alarm is activated, which allows turning on another distant alarm light, horn or other device. Finally,
the event of alarm is written into history.
The majority of possible faults are watched in three levels.
The alarm Warning (Wrn, yellow color) signals that the watched value approaches the dangerous level.
The alarm ShutDown (Sd, red color). The main protected parameters are the minimal oil pressure, minimal and
maximal speed, maximal cooling water temperature. The information about these analog values is brought into
the controller through analog inputs (AIN) or, in the case of an electronic engine (engine equipped by ECU), by
CAN bus.
Summary of Contents for InteliDrive FLX LITE
Page 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Page 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Page 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Page 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Page 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Page 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...