ID-FLX Lite Global Guide
195
Related FW
2.5.0
Related applications
Comm object
316
Description
Active input disables the Regulator PI loop and switches analog output to constant
.
R Reg Disable
Related FW
2.5.0
Related applications
Comm object
220
Description
DayCons is the counter which cumulates the instantanous consumption coming from ECU . It shows the
total consumption since the counter reset. Counte reset happen at the midnight of the controller clocks. LBI
Clear DayCons resets the counter DayCons.
Note:
The function works when the controller is connected to an ECU or in other case is consumption
counted from the changes of analog input value Fuel rate and setpoint
Clear DayCons
Related FW
2.5.0
Related applications
Comm object
221
Description
TripCon is the counter which cumulates the instantanous consumption coming from ECU. It shows the total
consuption since last reset by LBI Clear TripCon. This LBI resets the counter TripCons.
Note:
The function works when the controller is connected to an ECU or in other case is consumption
counted from the changes of analog input value Fuel rate and setpoint
Clear TripCons
Related FW
2.5.0
Related applications
Comm object
398
Description
FlowSwitch is protection to stop the engine in case the water not flow. Function is active in MAN and AUT
mode. Engine is switched to Cooling state when FlowSwitch is not closed within
after running (Ready to load) engine state activation. Function stops the engine in AUT mode with
FlowSwitch indication in Alarm list and stays in AUT mode after Fault reset.
Alarm list and History indication = "Cd Flow Switch" (CoolDown is third engine protection type in ID-Lite).
Machine state stays in Cooling even the LBI FLow Switch is activated again during Cooling period.
Flow Switch
Summary of Contents for InteliDrive FLX LITE
Page 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Page 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Page 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Page 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Page 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Page 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...