background image

InteliDrive DCU Marine - 3.0.0 Global Guide

75

4.4.9 InternetBridge-NT

Image 4.13 Dimensions of IB-NT

All dimensions are in mm.

Note:

Connect ID DCU HW 2.0 and newer + ID-COM with RS485 connected to IB-NT over RS485 works fine.

But: only one couple of balancing resistors has to be added on the whole RS485 line, and setpoint in ID-DCU

CommSet called

RS485 TermCSpd (page 122)

has to be set to 57600 bps.

Summary of Contents for InteliDrive DCU Marine

Page 1: ...rague 7 Czech Republic Tel 420 246 012 111 E mail info comap control com www comap control com Global Guide InteliDrive DCU Marine Expandable engine controller SW version 3 0 0 1 Document information 5 2 System overview 7 3 Application overview 24 4 Installation and wiring 38 5 Controller setup 79 6 Communication 96 7 Technical data 100 8 Appendix 104 ...

Page 2: ...ftware revision 16 2 1 8 How to find active alarms 16 2 1 9 How to select engine mode 16 2 1 10 How to view and edit setpoints 16 2 1 11 How to view measured data 17 2 1 12 How to view the History menu 17 2 1 13 Main screen indication 17 2 2 Controller configuration and monitoring 18 2 2 1 AirGate connection to the PC 18 2 2 2 Configuration steps 19 2 2 3 Direct conection to the PC 19 2 2 4 DriveC...

Page 3: ...ation architecture 50 4 2 2 Electronic engine without redundancy line 51 4 2 3 Engine without ECU mechanical engine 52 4 2 4 I CB wiring and configuration 52 4 2 5 ID RPU wiring 53 4 2 6 Recommended wiring acording to DNV rules 53 4 2 7 Wiring example Complete system without RPU 55 4 3 Getting started 55 4 3 1 How to install 55 4 3 2 Analog as Binary input 57 4 3 3 Analog as three state tristate b...

Page 4: ...Shared IO and Virtual IO 90 5 2 1 Virtual Binary Outputs VBOUT module 90 5 2 2 Shared virtual inputs and outputs 90 5 2 3 Distributed binary inputs and outputs 92 5 3 Multiple ECU modules support 93 5 3 1 Multi ECU Configuration with DriveConfig 93 6 Communication 96 6 1 InteliDrive Engine ECU communication 96 6 1 1 Example of standard J1939 engine 96 6 1 2 Tier 4 Final 96 7 Technical data 100 7 1...

Page 5: ...er can communicate with Engine Management System via the CAN serial line using standard J1939 or another KWP2000 communication protocol InteliDrive controllers are equipped with a powerful graphic display with icons symbols and bar graphs for intuitive operation which together with high functionality sets new standards in engine controls Engine functions Engine sequencing and control start stop wa...

Page 6: ...ant legal documents regulating protection of the intellectual properties TRIPS The End User and or ComAp s Distributor shall only be permitted to use this End User s Guide Manual with ComAp Control System Registered Products The Documentation is not intended and applicable for any other purpose Official version of the ComAp s End User s Guide Manual is the version published in English ComAp reserv...

Page 7: ...ce Cycle forward through engine operation modes OFF AUX EME HRB PRP Cycle backward through engine operation modes OFF AUX EME HRB PRP Deactivates the HORN Acknowledges faults and alarms Starts the engine in AUX EME HRB PRP mode Stops the engine in AUX EME HRB PRP mode hold time 1 sec ...

Page 8: ...cel of the cooling state by the 2nd push of the Stop button use LBI card of the DriveConfig tool and make the association of Access Lock to the Cooling logical binary output of the Source column It causes locking of the front panel buttons during the Cooling state 2 1 1 Controller screens There are three screen groups available on ID controller Measuring Setpoints History Measuring screen will be ...

Page 9: ...ts Service time 10 GPS speed value is shared from other devices Following screens appears depend on configuration Opt Analog 1 to Analog 8 Name value dimension active alarm is negative 1x IS AIN8 TC or Inteli AIN8 TC Opt IS BIN BI indication 1 to 8 Opt IS BIN BI indication 9 to 16 Opt IS BIN BO indication 1 to 8 Opt ECU values I Opt ECU values II Setpoints screens correspond with Setpoint table ab...

Page 10: ...fo Comment InteliDrive Product type ComAp 2018 Company name ID Controller type Serial 0200FFFF Controller serial number Sw ver 3 0 0 Software version Appl AUX Application Branch DCU Marine Firmware branch Statistic values It is calculated 1 Run Hours Each finished 60 minutes when engine is running 2 NumSuccStarts Each successful start starter is switched off due to RPM Starting RPM is calculated E...

Page 11: ...ng 10 digits and more If there is higher value it treats it as Signed long and show it as negative with minus sign Workaround If numbers with 10 digits has unlogically minus mark number should be recalculated History records Following table does not contain Wrn Sd and Fls messages from external units Events specification Protection type Information available on binary output Alarms Wrn Analog inpu...

Page 12: ... ID RPU Sd3 Broken wire WRN ID RPU Sd4 Broken wire WRN ID RPU Sd5 Broken wire WRN ID RPU Stop sol Broken wire WRN ID RPU Fuel sol Broken wire WRN Wrn RPM diff WRN YES Engine events Note Starts Button start Start from ID DCU MARINE panel CAN control Button start Start from ID DCU MARINE RS232 control Button start Start from InteliMonitor Remote start ID DCU MARINE binary input RemRepStart ID DCU MA...

Page 13: ... or IG IB IB NT ActCallCH1 OK Successful active call on channel 1 ActCallCH2 OK Successful active call on channel 2 ActCallCH3 OK Successful active call on channel 3 ActCallCH1Fail Failure of active call on channel 1 ActCallCH2Fail Failure of active call on channel 2 ActCallCH3Fail Failure of active call on channel 3 Extern start Manual engine starter handling Engine stop Engine changed state from...

Page 14: ... ON Sd Override function activated SdOverride OFF Sd Override function deactivated Note Value name can t exceed 11 characters to be recorded to History file with prefix Wrn Fls etc Longer names characters are canceled Corresponding Sd BINx Sd BOUTx or Sd AINx is indicated in Alarm list and history record when communication with any extension units IS BIN IS AIN IGS PTM is interrupted Example When ...

Page 15: ...10 sec to Main screen Language selection or Language screen Language screen exit Enter The system supports following character sets West European Code page 1252 in Windows East European Code page 1250 in Windows Russian Code page 1251 in Windows Turkish Code page 1254 in Windows Simplified Chinese Code page 936 in Windows Note If the configuration table has a code page that is not supported in the...

Page 16: ...EASUREMENT menu Press and you will see the list of all active alarms with the number of alarms at the top right corner Inverted alarms are still active Non inverted alarms are not active but not yet confirmed Press Fault reset accepts alarms of active visible screen Non active alarms immediately disappear from the list Active alarm list appears on the screen when a new alarm comes up and Main MEAS...

Page 17: ...the Page button repeatedly will scroll the user through the menu screens Select the MEASUREMENT screen Use and to select the screen with requested data 2 1 12 How to view the History menu 1 Pressing the Page button repeatedly will scroll the user through the menu screens Select the HISTORY screen 2 Use or to select a requested record 3 Use Enter to select requested screen record items within displ...

Page 18: ...tatic IP address The controllers connect by InternetBridge NT module to the AirGate server and cyclically ask whether there is a connection request from a client or not On the other side the clients only ComAp PC applications DriveConfig DriveMonitor InteliMonitor and WebSupervisor connect to the AirGate server instead of connecting directly to the controller The server then creates a tunnel betwe...

Page 19: ...isplays Manage ECU Fault codes Add Translate the language Translator The Translator enables to translate all or some texts to up 5 languages that could be available in controller Controller language can be changed from panel buttons It is possible to operate different languages on each ID DCU MARINE Remote panel and InteliMonitor Note Check all screens if some texts are not shortened 2 2 3 Direct ...

Page 20: ...n file with firmware in controller Note Configuration aid file does not contain the History record when had been read from the InteliDrive controller by DriveConfig Note To load History file from InteliDrive use InteliMonitor software only Application file archive There exists one binary type of configuration file only Config file aid contains Complete I O configuration include extension modules i...

Page 21: ...Multiply Registers Function 6 Write Single Register Function 16 Write Multiply Registers The response to an incoming message is sent with minimum 4 096 ms delay after message reception The complete description of Modbus communication protocol can be found in Modbus Protocol Reference Guide PI MBUS 300 and Open Modbus Specification Release 1 0 Both documents are available from web site at http www ...

Page 22: ...ce that level password or higher has been entered if the change is made from InteliMonitor PC tool Password level 3 must be entered at first to change any password if the change is made by controller front panel buttons Note Engine Cmd Password protection blocks Engine commands Start Fault reset Horn reset from front panel ID DCU MARINE by InteliMonitor Modbus ID DCU MARINE InteliVision 5 CAN Back...

Page 23: ...0 HW switchableto IO16 0 16 Binary inputs I IO8 8 IS BIN 16 8 16 configurable galvanically separated inputs 8 configurable outputs IS BIN16 8 Inteli AIO9 1 9 Analog inputs 4x DC 4x thermocouples 1x R I AIO9 1 IS AIN8 8 Analog inputs packed in a rugged metal unit IS AIN8 IS AIN8TC 8 analog inputs for thermocouple measurement supports J K L types IS AIN8TC IGS PTM 8 Binary inputs 8 Binary outputs 4 ...

Page 24: ...tart Stop ID DCU MARINE Start Stop button EME Emergency DCU MARINE EME 3 0 0 aid OFF EME Standby BI Blackout Start BI Remote Start BI Remote Stop BI Rem Start Stop ID DCU MARINE Start Stop button CMB Combined DCU MARINE CMB 3 0 0 aid OFF EME HRB Standby Manual EME HRB BI Blackout Start BI Remote Start BI Remote Stop BI Rem Start Stop ID DCU MARINE Start Stop button PRP Propulsion DCU MARINE PRP 3 ...

Page 25: ...ed based on real failure in logical 0 only for electronic units Fls will not be triggered if binary is in logical 1 and for physical inputs Protections Note There are visible only the first two bar graph marks for protection limits indication on ID DCU MARINE screen ...

Page 26: ... Guide 26 How to configure analog input window protection 1 Switch DriveConfig to EXPERT mode 2 Configure standard two level analog protection 3 Add another protections in EXPERT window There can be set the same delay for all four limits ...

Page 27: ... closed the Loadsharing ThrottlePos value is adjusted to the Loadsharing Back Up Speed the ThrottlePos value change is influenced by ramp Loadsharing RQSP Ramp When binary input Fire Speed is closed the Clutch is disconnected and the Loadsharing ThrottlePos is set to Engine params FireAlarmSpeed the ThrottlePos value change is influenced by ramp Loadsharing RQSP Ramp For 100 of Engine Values Speed...

Page 28: ...ote Set Engine Params Idle offset 0 and Engine Protect OverloadSpLim 100 to disable Overload protection functionality i e if the protection is not requested by an application Under speed protection Under speed protection is activated 5 sec after RPM Engine params Starting RPM Engine underspeed is detected when RPM drops below setpoint Engine Protect UnderSpeed ...

Page 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...

Page 30: ... EME CMB and PRP Auxiliary mode AUX archive AUX mode is designed for auxiliary engines Controller starts and stops the engine according to the binary inputs Blackout Start or Remote Start Rem Start Stop Remote Stop or to the ID DCU MARINE Start Stop buttons Binary inputs Blackout Start and Remote Start and Remote Stop are inactive in LOC Local mode All engine protections and all configured shutdow...

Page 31: ...LOC Local mode All engine protections and all configured shutdown protections are active Controller continuously monitors all available engine parameters oil pressure water temperature RPM fuel level etc The engine will stop and activates Common Warning and Common Shutdown outputs and writes record to the history file when detects any active Shut down alarm This condition can be signaled by Active...

Page 32: ... This way can be configured protection to any ID DCU MARINE internal value or more levels external indication Example of Universal state1 configuration to Engine speed Warning for Engine speed 1600RPM 1s This configuration is available in DriveConfig Expert mode 3 2 ID RPU Image 3 1 Redundancy protection unit Note Maximal torque to tight main screw is 0 25 Nm ...

Page 33: ...ower supply switching for the control system ID RPU monitors InteliDrive central unit and in the case of fail switches itself to the backup mode or Emergency backup mode and protects the engine using its own binary EMERGENCY STOP and SHUT DOWN inputs and FUEL and STOP SOLENOID outputs The ID RPU unit has three operational modes Normal ID DCU MARINE is working and periodically sends the watchdog im...

Page 34: ... no I O state or Broken wire LED indication on ID RPU module All indications are visible on ID DCU MARINE screen include Alarm list and History record Binary input Emergency stop No Broken wire detection The input logic is Normally Closed Input is active in all EME AUX and PRP modes No LED indication Binary output COMM SD Output indicates any shutdown Alarm Normal mode the output is controlled fro...

Page 35: ...tchdog ID DCU MARINE periodically 0 2s sends an impulse to the ID RPU ID RPU backup mode is activated after 1s without watchdog pulse Required CtrlHeartBeat rate is 100ms 100ms Overspeed protection The ID RPU overspeed protection is active in the case of ID DCU MARINE fail only backup mode Overspeed limit can be set by DIP switch accessible after cover removal ID RPU Emergency Auxiliary mode opera...

Page 36: ...Prefix X range C Prefix 2016 to 8128 32 1000 504 to 2032 8 0100 126 to 508 2 0010 1 to 127 0 5 0001 Table 1 X 3200 is in the range 2016 to 8128 C 32 Prefix 1000 3 Step Speed preset 3200 32 1 101 01100101 in binary format 4 Step set Prefix 1000 and Speed preset 01100101 RPMover Gear teeth Prefix Speed preset DIP8 1800 150 1000 141 10001101 1800 120 1000 113 01110001 1800 60 0100 226 11100010 1000 3...

Page 37: ...InteliDrive DCU Marine 3 0 0 Global Guide 37 64 01000000 128 10000000 255 11111111 6 back to Application overview ...

Page 38: ...an overall enclosure rubber seal for IP 65 Technical data page 100 Left RED Active alarm indication Blinks when new alarm is activated Steady lights after Fault reset confirmation when alarm is still active Disappears after Fault reset confirmation when alarm is inactive Right GREEN Engine running indication Light when engine is running Front panel LED Note Please check the last software version ...

Page 39: ...g via electronic signal J1939 or Modbus protocol Generally can read binary and analog values from engine inputs and transmit binary outputs e g Start Stop commands and analog outputs e g Speed request ECU size count of input and output resources are configurable and depends on controller possibilities 4 1 4 ID DCU MARINE dimensions ID COM and ID SCM are mounted directly to ID DCU MARINE case ...

Page 40: ...s 0 25 Nm 4 1 5 ID COM terminals Communication interface ID COM is mounted directly to ID DCU MARINE box The new standard ID COM will only be with the RS485 interface Note Maximal torque to tight main screw is 0 25 Nm CAN1 Extension modules EMS IS AIN8 TC IS BIN16 8 IGS PTM IGL RA15 CAN2 Intercontroller I LB IG IB IB NT others ID DCU MARINE ...

Page 41: ... this case connect Extension modules CAN1 directly to Extension modules port ID COM on ID DCU MARINE 9 pin connector 5 H 9 L 4 1 6 ID DCU MARINE terminals RPM Primary RPM BI1 to BI14 Binary inputs active when closed to minus power supply BO1 to BO14 Binary outputs Low side switch 0 5 Amps each D D plus terminal AIN1 to AIN4 Analog inputs group 1 AIN5 AIN5 AIN6 AIN6 AIN7 AIN7 AIN8 AIN8 Analog input...

Page 42: ...rd ID DCU and ID MCU without LT extension The only one low temperature sensitive part is the controller display ID DCU LT version contains a preheating foil on the display activated below 5 C measured on the PCB Heating is switched off when controller power supply is below 10VDC together with display backlight 4 1 8 ID RPU terminals Redundant Protection Unit ID RPU is mounted directly to ID DCU MA...

Page 43: ...ol module ID SCM module is interface module for InteliDrive controller application Module is mounted directly to ID DCU MARINE controller case Module power supply 8 to 36VDC Inputs RPM1 RPM2 Two inputs for frequency e g flow measuring Expected sensor is magnetic pickup with maximal frequency range up to 8 kHz The output values SCM Freq1 SCM Freq2 calculation use setpoints SCM unit FreqRate1 and Fr...

Page 44: ...g to IMP1 and IMP2 inputs Active NPN sensor wiring to IMP1 and IMP2 inputs Note Maximal torque to tight main screw is 0 25 Nm Outputs 4 1 10 ID SCM1 Technical data Power supply internal supply from ID DCU MARINE 8 to 36 VDC Operating temperature range 40 C to 70 C Number of analog outputs 1 no galvanic separation ...

Page 45: ...5 CAN is offered in two hardware modifications InteliVision 5 CAN InteliVision 5 CAN Backlit The only HW difference between two versions is presence of standard or backlight keyboard version i e if there is present a feature of back lighted buttons or not Both versions are IP65 protected from all sides equipped with binary output switch for HORN signaling CAN interface is galvanically separated Th...

Page 46: ...connector wiring 1 GND 5 UBatt 2 A B IN 6 CAN L 3 BO A 7 COM 4 BO B 8 CAN H 1 5 Power supply 8 36VDC 6 8 CAN bus with galvanic separation 3 4 Binary output configured for Horn function It is Solid State Relay with galvanic separation Max 36VDC 0 5A like free contact ...

Page 47: ...stive pot for continuous backlit change 0Ω 0 2400Ω 100 Or just place contact to switch between 0 and 100 intensity Note It is possible to connect up to five InteliVision 5 CAN or four InteliVision 8 displays to common CAN2 bus The display addresses must be different in this case 4 1 12 InteliVision 8 InteliVision 8 Marine ...

Page 48: ...olution and delivers high visibility of all engine data monitoring information and trend history in a bright colorful and impressive industrial capacitive touch based design The Plug and Play solution ensures the User buy the display unit and controllers puts it together and it works for most of the applications No additional programming skills or learning complicated tools are needed The display ...

Page 49: ...iDrive DCU Marine 3 0 0 Global Guide 49 Image 4 2 InteliVision 12Touch dimensions Image 4 3 Wiring example ID DCU Marine to InteliVision 12Touch Note For more information see InteliVision 12Touch Globa guide ...

Page 50: ...INE controllers and or IG MU Direct cable analog modem or GSM modem interface and or IG IB Internet interface and or IB NT and or The data rate is selectable in two levels 250 kBd for 200 meters line and 50 kBd for 900 meters line CAN bus Connection rules CAN bus line must be connected in series from one unit to the next no star no cable stubs no branches both ends must by the 120 Ω internal or ex...

Page 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...

Page 52: ...I CB configuration associates selected values from ECU database received from Engine Control Unit to selected CAN addressees fictive IS AIN IS BIN inputs and outputs 2 Configure corresponding CONTROLLER CAN addresses in PC configuration tool 3 Configure separate inputs and outputs in corresponding Analog Binary inputs outputs in PC configuration tool Note In case of CAT engines there is RS232 conn...

Page 53: ...y DriveConfig sw Battery minus terminals are separated See also Recommended wiring acording to DNV rules page 53 4 2 6 Recommended wiring acording to DNV rules There is recommended wiring diagram of InteliDrive DCU Marine controller ID RPU module following latest DNV requirements for mutual independency of control alarm and safety systems InteliDrive DCU Marine provides features of control and ala...

Page 54: ...ut 2 Actuator controlled by ID DCU BOx output configured to Stop Solenoid function Note Emergency stop button contacts type NC Normally Closed can be directly incorporated into circuit controlling ID RPU EM STOP input It is also acceptable to use relay NC contacts in the circuit connected to ID RPU EM STOP input relay coil is controlled by emergency stop circuit in case of NO Normally Opened emerg...

Page 55: ...nents shall be used within marked electrical ratings see chapter Technical data Binary output protections Do not connect binary outputs directly to DC relays without protection diodes Use protection diodes even if the relays are not connected directly to controller outputs Use a fast recovery 3A 50V diodes Image 4 4 Example of controller protection ...

Page 56: ... and binary inputs should be provided with shielded cables especially when length 3m Grounding To ensure proper function The shortest possible piece of wire should be used when grounding the controller Use cable min 2 5mm2 The terminal of the battery has to be properly grounded Magnetic pick up To ensure proper function use a shielded cable Be aware of interference signal from Speed governor when ...

Page 57: ...to protect against atmospheric discharges Install separate conductors for signal and power inputs Allow for conductor voltage drop when determining conductor size All power supplies must have common ground When there is a potential risk of the controller being subjected to conditions outside its capabilities an outside protection device should be used 4 3 2 Analog as Binary input To use Analog inp...

Page 58: ...ctive Y Y 0 250 Ω Y Y 0 2400 Ω Y Y 0 4 V Y 0 5 V Y 1 V Y 0 100 mV Y Tristate Y Y 4 3 5 Analog Sensors availability with extension modules Table of supported sensors on various modules Do not configure sensors that are not supported on the input IS AIN8 I AIN8 IS AIN8TC I AIN8TC I AIO 9 1 IGS PTM not used analog input Y Y Y Y Y Y user curves Y Y Y Y PT100 C Y Y Y PT1000 C Y Y Y NI100 C Y Y Y NI1000...

Page 59: ... nc K C Y Y Y Y Thermo nc L C Y Y Y Y Thermo nc J F Y Y Y Y Thermo nc K F Y Y Y Y Thermo nc L F Y Y Y Y 0 5 V Y 0 10 kΩ Y 65 V Y 75 mV Y Note IGS PTM has hardware range 0 20mA but offered sensor in DriveConfig is 20mA IGS PTM has hardware range 0 250Ω only DriveConfig offers correct sensor for I O configuration but for User define input curve only sensor 0 2400Ω Note Fahrenheit sensors are support...

Page 60: ...y output separation In some special cases e g when Relays plus terminal is disconnected via EMERGENCY STOP contact the binary outputs must be separated using diodes to avoid false Binary output LED indication In the Example below when EMERGENCY STOP contact is opened the BO3 LED should light without separating diode SD3 even if the BO3 output is opened ...

Page 61: ...terminal COM has to be connected to ID minus Power supply terminal Mixed connection of ID DCU MARINE analog inputs AI2 AI7 current sensor AI1 AI5 resistive sensor AI3 AI8 voltage input AI6 thermocouple voltage AI4 Not used Mixed connection of InteliDrive analog inputs AI1 AI2 AI5 AI6 resistive sensor AI3 AI7 binary input AI4 AI8 three state input Analog input common terminal COM has to be connecte...

Page 62: ... sensor AI5 to AI8 Resistance sensor Current Measurement Jumper on pins 1 2 Voltage thermocouples AI5 AI8 measurement Jumper on pins 2 3 Resistance measurement Jumper on pins 3 4 Note Maximal voltage on controller Differential analog inputs AI5 to AI8 is in the range 2 to 5 VDC against minus power supply terminal ...

Page 63: ...g in InteliDrive controller See Sensor availability in table below Resolution Output value reading resolution DriveConfig indicates when Resolution is out of the value range Sensor range Full output value reading range for 20 mA current 250 Ω 2400 Ω resistive 1 V 4V 5V 100 mV voltage sensor Protection Select from the list Configure two protection levels as standard or more levels window protection...

Page 64: ... mA input Current 1 2 0 250 Ω 0 2400 Ω For 250 or 2400 Ω Input Resistance 3 4 Tristate Resistance 3 4 0 to 4 VDC Adjustable Voltage 2 3 Sensors available on ID DCU MARINE AI5 AI8 Resolution Sensor range HW jumper Pt100 C Pt1000 C Ni100 C Ni1000 C Pt100 F Pt1000 F Ni100 F Ni1000 F Fix not configurable Resistance 3 4 Thermocpl J C Th K C Th C Thermocpl J F Th K F ThL F Fix not configurable Voltage 2...

Page 65: ...Note HW configuration CU 0 1 V can be used for characteristics 1 V but this characteristics can be configured to AI5 to AI8 inputs only Sensor range gray background automatically follows the User sensor characteristics zero value at the above picture is not important Conversion from 20 mA to 100 request ...

Page 66: ...aph indicates only positive values 0 to 100 Conversion from 20mA to 100 request with User sensor Sensor characteristics 20mA works in full range on ID DCU MARINE AI5 to AI8 only ID DCU MARINE AI1 to AI4 measures 0 to 20 mA range only 1 Create User sensor as below 2 Configure user sensor instead default 20mA sensor 3 Configure Bargraph 100 to correspond User sensor Bargraph indicates full 0 to 100 ...

Page 67: ...e 3 0 0 Global Guide 67 2 Configure user sensor instead default 20mA sensor User sensor examples Availability Configuration AI1 to AI4 AI5 to AI8 Analog input jumper 1 2 current 0 20mA 600 AI1 to AI4 AI5 to AI8 4 20mA 100 0 ...

Page 68: ...per 2 3 voltage 0 1V 10 000 AI5 to AI8 0 100mV 100 00 AI1 to AI4 AI5 to AI8 Analog input jumper 3 4 resistance 0 1200 Ω 100 Note It is possible to set up to 30 points non linear sensor characteristics Connect external resistors voltage divider to extend input voltage range ...

Page 69: ...lick here 4 4 1 Inteli AIN8 69 4 4 2 Inteli AIN8TC 70 4 4 3 Inteli IO8 8 can be switched to IO16 0 70 4 4 4 IS BIN 16 8 71 4 4 5 Inteli AIO9 1 71 4 4 6 IS AIN8 72 4 4 7 IS AIN8TC 73 4 4 8 IGS PTM 74 4 4 9 InternetBridge NT 75 4 4 10 I CB Communication bridge 76 4 4 11 I AOUT8 76 4 4 1 Inteli AIN8 Image 4 5 Dimensions of Inteli AIN8 Inteli AIN8 unit can be mounted on DIN rail 35 mm All dimensions a...

Page 70: ...ge 4 6 Dimensions of Inteli AIN8TC Inteli AIN8TC unit can be mounted on DIN rail 35 mm All dimensions are in mm 4 4 3 Inteli IO8 8 can be switched to IO16 0 Image 4 7 Dimensions of Inteli IO8 8 Inteli IO8 8 unti can be mounted on DIN rail 35 mm All dimensions are in mm ...

Page 71: ...rictly fixed to module position in general meaning is position equal module address ID DCU Marine support compensation of cold end up to 4 modules In case AIO9 1 temperature compensation could be used only for 2 units 2 modules multiple 2 occupied positions gives 4 modules in total Example of most effective configuration Address 1 AIN8 TC module Thermo nc Address 2 AIO9 1 module Thermo nc another ...

Page 72: ...Guide 72 Image 4 9 Dimensions of Inteli AIN8 Inteli AIO9 1unit can be mounted on DIN rail 35 mm All dimensions are in mm 4 4 6 IS AIN8 Image 4 10 Dimensions of IS AIN8 IS AIN8 unit can be mounted on DIN rail 35 mm All dimensions are in mm ...

Page 73: ...InteliDrive DCU Marine 3 0 0 Global Guide 73 4 4 7 IS AIN8TC Image 4 11 Dimensions of Inteli AIN8 Inteli AIN8 unit can be mounted on DIN rail 35 mm All dimensions are in mm ...

Page 74: ...InteliDrive DCU Marine 3 0 0 Global Guide 74 4 4 8 IGS PTM Image 4 12 Dimensions of IGS PTM All dimensions are in mm IGS PTM unit can be mounted on DIN rail 35 mm ...

Page 75: ...B NT All dimensions are in mm Note Connect ID DCU HW 2 0 and newer ID COM with RS485 connected to IB NT over RS485 works fine But only one couple of balancing resistors has to be added on the whole RS485 line and setpoint in ID DCU CommSet called RS485 TermCSpd page 122 has to be set to 57600 bps ...

Page 76: ...tion package I CB wiring and configuration 1 Configure I CB using I CBEdit software Configured I CB behaves like fictive IS AIN and IS BIN units I CB configuration associates selected values from ECU database received from Engine Control Unit to selected CAN addressees fictive IS AIN IS BIN inputs and outputs 2 Configure corresponding controller CAN addresses and tick in PC configuration tool 3 Co...

Page 77: ...default AGND terminals are on the same potential Number of analog outputs 8 no galvanic separation Type of analog outputs jumper selectable U 0 to 10VDC 1 max 5 mA I 0 to 20 mA 1 max 500 Ω p pwm 1200 Hz 5V level max 10 mA Power supply 8 to 36 VDC Current consumption 100 300 mA at 24 VDC Communication interface CAN1 with jumper selectable address 1 to 4 Jumper selectable terminating resistor 120 Ω ...

Page 78: ...0 to 20 mA U 0 to 10 VDC LED Indication Green LED is located near the power supply connector I AOUT8 module state LED Pwr No power supply Dark Memory fail Fast blink 100 100 ms Communication fail Slow blink 300 300 ms Communication fail Continuous light Wiring and jumer setting example Voltage output 0 to 10 VDC Pwm output 1200 Hz Current output 0 to 20 mA Current output 0 to 20 mA Current output ...

Page 79: ...rottlePos Info ECU DiagSource Timer val PasswordDecode Statistics NumSuccStarts NumUnscStarts Service time All function limits and analog outputs must follow input analog value format e g input value is 0 0 to 10 0 bars then setpoint limit is e g 3 2 Any time and delay limit is in 0 1s step in the range 0 1 to 3276 7 sec PLC consistency check indicates incorrect PLC configuration Binary List conta...

Page 80: ...or in DriveConfig context help F1 key when a PLC function is selected IMPORTANT Logic for controlling the motor can t be locked in PLC Certification authority can ask for access to the content locked this way PLC Function Selection Available Number of available blocks in ID DCU Marine 3 0 0 OR AND 128x XOR RS 128x Comp Hyst 24x Comp Time 8x Comp Win 16x Math Fc 16x Ext Math Fc 8x ...

Page 81: ...rive DCU Marine 3 0 0 Global Guide 81 PLC Function Selection Available Number of available blocks in ID DCU Marine 3 0 0 Interpol Fc B 8x Nonlin I Fc 4x Math AxB C 8x PID Bin 4x PID Ana C 8x Ramp 4x Up Down 4x ...

Page 82: ... Marine 3 0 0 Global Guide 82 PLC Function Selection Available Number of available blocks in ID DCU Marine 3 0 0 Inc Dec 2x Mov Avg 4x Timer 4x Delay 16x Delay B 8x Ana Switch 16x Force Hist 4x Force Prot 16x Jump 8x ...

Page 83: ... Let suppose a diesel compressor The engine speed is controlled via ID SCM Speed governor analog output no data communication InteliDrive measures output pressure Required function Based on adjustable pressure limits ID controller switch the engine between RPM1 to RPM2 When Pressure drops below Pressure ON limit engine increases from RPM1 to RPM2 and after Pressure increases above Press OFF limit ...

Page 84: ...figuration steps 1 Start DriveConfig and open default archive ID DCU X aid 2 Pressure measuring configure pressure sensor characteristic suppose range 0 to 10 0 Bars on ID DCU MARINE Analog input 4 Wrn and Sd protection limits should be adjusted over Pressure OFF limit ...

Page 85: ...Drive DCU Marine 3 0 0 Global Guide 85 3 Go to PLC window and drag drop PLC functional block Comp Hyst double click the block 4 Configure Comparator Input click on button and select input value from the list ...

Page 86: ...N Input OFF as PLC setpoints 6 Edit setpoint name in PLC setpoints list Result look like this 7 Drag drop PLC functional block Ana Switch configure Input 1 and Input 2 as PLC setpoints and edit the setpoint names to RPM 1 and RPM 2 8 Configure binary Input SW PLC values PLC Bout 1 1 ...

Page 87: ...igure output convert Low limit 0 RPM 0 00V output and High output convert limit 2000 RPM 10 00V output Speed governor output characteristics for Lo limit and Hi limit setting above Speed governor output voltage in this case when RPM1 500 and RPM2 1800 is 9V when pressure is low and 2 5V when pressure is high 11 Final PLC layout in DriveConfig ...

Page 88: ...ifferent colours All existing passwords are entered all PLC sheets with password are unlocked Any but not all existing passwords are entered any but not all PLC sheets with password are unlocked No existing password is entered or no password exists all PLC sheets with passwords are locked In Passwords window user can Login by entering correct password and clicking red button Logout by clicking gre...

Page 89: ...rd is used for any PLC sheet password will be removed from appropriate PLC sheets user has to confirm this Correct password must be entered If password is not used for any PLC sheet password is removed immediately without warning No need to enter correct password To assign password to the PLC sheet click on assign icon in title of PLC sheet ...

Page 90: ...ules are available One of them is Virtual Binary Outputs module VBOUT which enables use of Prg states binary signals with the built in PLC Prg states signal can not be directly configured as a PLC module input Therefore it is necessary to use VBOUT module as interface between a Prg state signal and a PLC module Up to 4 VBOUT modules are available each VBOUT modules represents 8 binary output signa...

Page 91: ...ction appears because SHBIN or SHAIN will be missing See the figure below for more information IMPORTANT For proper function of Shared Binary and Analog Inputs and Outputs only one source of Shared Binary or Analog Outputs must be configured i e it is not possible to configure in one controller SHBOUT1 and to another one as well SHBOUT1 Note Controller sends Shared Binary Outputs each 100ms if the...

Page 92: ...the CAN address of the controller e g the controller with address 5 will be broadcasting DISTBOUT 05 which can be received if module DISTBIN 05 is configured in another controller Up to 32 DISTBIN modules can be configured meaning that the controller will be receiving all DISTBOUT from all the controller even his own It is not possible to change the name of DISTBIN inputs or add protections In the...

Page 93: ...modules CAN 1 J1939 for CAN bus communication usually J1939 protocol based communication RS485 for Modbus communication It is possible to combine the interfaces e g engine ECU connected via RS485 with ignition connected via CAN1 5 3 1 Multi ECU Configuration with DriveConfig Use Modules card in DriveConfig to configure support of ECU modules with the Insert Remove buttons IMPORTANT Be aware that i...

Page 94: ...le Module name user adjustable string with up to 10 characters Default values are ECU ECU 1 to ECU 9 depending on order in which are modules added Module address user adjustable number from 0 to 255 which defines address of configured module Default option is Default X X stands for actual address value which comes from ESC and is assigned to module when the default option is used It is recommended...

Page 95: ...display hide module related screens Display data as information how are analog values displayed Analog inputs Number of analog input values available with module Note Total number of available analog input values is limited to 160 with all configured modules e g 4 modules with 40 inputs would use all available inputs Analog outputs Number of analog output values available with module Note Total nu...

Page 96: ...lter Diff Press bar Battery Potential Voltage V Fuel Delivery Pressure bar Engine Oil level Crankcase Pressure bar Coolant Pressure bar Coolant Level Fault reset accepts confirms diagnostic message removes inactive message form ECU Alarm list only when ECU Alarm list is visible Note Fault reset button is screen sensitive It is active only on selected actual controller screen 6 1 2 Tier 4 Final Tie...

Page 97: ...reen is then shown until operator switch it to another one Alarmlist screen has lower priority so even new alarm appears After treatment screen is still displayed To avoid displaying blank screen inactive lamps are represented by dotted icons For no active lamp the screen shows all dotted icons Please see examples below Image 6 1 Example of active Tier 4 Final screen Image 6 2 Example of inactive ...

Page 98: ...tive icon Inactive icon Notes Amber warning lamp Note This value can light or blink on both frequencies Red stop lamp Note This value can light or blink on both frequencies Engine wait to start lamp DPF SCR lamp command Note DPF Diesel Particulate Filter SCR Selective Catalytic Reduction This lamp also activates alarm After treatment Exhaust system high temperature lamp command Note This lamp also...

Page 99: ...or blink on both frequencies This lamp also activates alarm After treatment Fluid tank low level indicator Note This lamp also activates alarm After treatment DPF regeneration inhibited Note Indicates the state of diesel particulate filter active regeneration inhibition This lamp also activates alarm After treatment 6 back to Communication ...

Page 100: ...te Time information only Operating temperature ID DCU MARINE 20 to 70 C Operating temperature ID DCU LT 40 to 70 C Storage temperature 30 to 80 C Humidity 95 without condensation Flash memory data retention time 10 years Protection front panel IP65 Standard conformity Low Voltage Directive EN 61010 1 95 A1 97 Electromagnetic Compatibility EN 61000 6 2 October 2001 EN 61000 6 4 October 2001 IEC 605...

Page 101: ...mum input voltage 50 Veff Minimum measured frequency 4 Hz Maximum measured frequency 10 kHz min input voltage 6Vpk pk Frequency measurement tolerance 1 5 Speed pick up input Max D output current 300 mA Guaranteed level for signal Charging OK 80 of supply voltage D function Group 1 AI1 AI4 Number of inputs 4 unipolar Resolution 10 bits Jumper selectable range V Ω mA Maximal resistance range 2500 Ω ...

Page 102: ...red value Current measurement tolerance 0 5 0 5 mA out of measured value Maximal distance 10 m Speed 19 2 kBd RS232 interface 7 2 CAN bus interface Max CAN bus length Basic setting CAN bus mode 250 kBd 200m Basic setting CAN bus mode 50 kBd 900m Nominal impedance 120Ω Cable type twisted pair shielded Following dynamic cable parameters are important especially for maximal 200 meters CAN bus length ...

Page 103: ...iceBus for Allen Bradley DeviceNet 3105A Paired EIA Industrial RS485 cable LAPP CABLE see http www lappcable com Unitronic BUS DeviceNet Trunk Cable Unitronic BUS DeviceNet Drop Cable Unitronic BUS CAN Unitronic FD BUS P CAN UL CSA 6 back to Technical data ...

Page 104: ...InteliDrive DCU Marine 3 0 0 Global Guide 104 8 Appendix 8 1 Controller objects 105 6 back to Table of contents ...

Page 105: ... configuration procedure IMPORTANT Do not perform repeated writing of setpoints e g do NOT have a MODBUS watchdog system where PLC periodically writes down a figure into register and then reads the figure The setpoints are stored in EEPROM memory which can be overwritten up to 100 000 times without risk of damage or data loss however it may become damaged when allowed number of writing cycles is e...

Page 106: ...InteliDrive DCU Marine 3 0 0 Global Guide 106 For full list of setpoints go to the chapter List of setpoints page 107 6 back to Controller objects ...

Page 107: ... Ramp 132 FireAlarmSpeed 132 EnLocalSpeed 132 Local Speed 133 Group of setpoints Engine protection Horn Timeout 134 RunOnlyBlkDel1 134 RunOnlyBlkDel2 135 RunOnlyBlkDel3 136 BinInp Delay 1 137 BinInp Delay 2 137 BinInp Delay 3 138 ForceBlockDel1 139 ForceBlockDel2 139 ForceBlockDel3 140 Overspeed 140 UnderSpeed 141 MinLoadSpeed 141 Batt V 141 Batt V 142 Batt Volt Del 142 OverloadSpLim 142 Overload ...

Page 108: ... SummerTimeMod 169 EnTimeSync 169 Group of setpoints ID SCM unit FreqRate1 170 FreqRate2 170 TransferRate1 170 TransferRate2 171 Group of setpoints DetCon20 DelayLoadRed 171 DecreaseRamp 172 IgnRedLimit 172 ImmStopLimit 172 TimingRedGain 173 6 back to Controller objects InteliDrive DCU Marine 3 0 0 Global Guide 108 ...

Page 109: ...closed 15 minutes after the last key has been depressed or when wrong value of setpoint is set Note It is possible to protect remote Start Stop commands from InteliMonitor as well This three level command protection can be configured from DriveConfig EnterPassword Password is a four digit number Only setpoints associated with the entered password level can be modified Use or to select the desired ...

Page 110: ...t Commands window 3 Set Password 0 no protection or level 1 or 2 or 3 Note Engine commands password protection works according to the description above from firmware version ID DCU MARINE 2 1 and firmware versions of remote displays listed below In older firmware versions Engine Cmd group contains also Stop command commands from ID DCU MARINE local panel buttons directly on the controller were not...

Page 111: ...cters long and have to be entered manually using InteliMonitor software Note Engine name is not changed when new archive is loaded Check Engine name after firmware upgrade Engine Name 6 back to List of setpoints Setpoint group Basic settings Related FW 3 0 0 Range units Default value OFF Step Comm object 8315 Related applications All Config level Standard Setpoint visibility Always Description Mod...

Page 112: ... 1 Comm object 10920 Related applications All Config level Standard Setpoint visibility Always Description Number of teeth on the engines flywheel for the pick up connected to ID RPU RPU Gear Teeth 6 back to List of setpoints Setpoint group Basic settings Related FW 3 0 0 Range units 30 4000 RPM Default value 1500 Step 1 Comm object 8253 Related applications All Config level Standard Setpoint visi...

Page 113: ...e BIN INPUT ISOCH DROOP mode is switched via Binary input BI Droop DROOP when closed Governor Mode 6 back to List of setpoints Setpoint group Basic settings Related FW 3 0 0 Range units IDLE NOMINAL BIN INPUT Default value IDLE Step Comm object 10336 Related applications All Config level Standard Setpoint visibility Always Description Activates deactivates the logical binary output Nominal Sw that...

Page 114: ...c setting Nominal RPM must correspond to ECU Nominal RPM for 100 Throttle position in PRP and 50 in AUX Speed Select 6 back to List of setpoints Setpoint group Basic settings Related FW 3 0 0 Range units AUTO INTERNAL ECU Default value AUTO Step Comm object 8630 Related applications All Config level Standard Setpoint visibility Always Description AUTO controller displays valid running hours value ...

Page 115: ...21 Related applications All Config level Standard Setpoint visibility Always Description Timeout for ID display backlight automatic switch off Zero setting disables display backlight switch off Backlight is automatically switched on after any key press or Alarm activation Note LightTimerOff setpoint influences the Remote panel not master controller when changed on Remote panel LightTimeOff 6 back ...

Page 116: ...group Basic settings Related FW 3 0 0 Range units Never Mon Fri Mon Sat Mon Sun Sat Sun Default value NEVER Step Comm object 10045 Related applications All Config level Standard Setpoint visibility Always Description Logical binary output Timer Active is closed when actual time is over the Timer ON and opened when actual time is over Timer OFF The function depends on Timer Repeat settings The outp...

Page 117: ... FW 3 0 0 Range units 32C 8C Default value 32C Step Comm object 24499 Related applications All Config level Standard Setpoint visibility Always Description Inter controller IG IB IB NT CAN2 bus speed selection 32C High speed CAN 250 kBd applicable with up to 32 controllers CAN bus limited up to 200 meters 8C Low speed CAN 50 kBd applicable with up to 8 controllers CAN bus limited up to 900 meters ...

Page 118: ...ting when opening Direct or Modem connection ControllerAddr 6 back to List of setpoints Setpoint group Comms Settings Related FW 3 0 0 Range units ENABLED DISABLED EXTERNAL Default value ENABLED Step Comm object 10353 Related applications All Config level Standard Setpoint visibility Always Description This setpoint is used to disable reading of diagnostic codes from ECU if an external diagnostic ...

Page 119: ...ly after 5 min of inactivity and next communication request from the same terminal is considered as a new connection When logging is enabled in certain conditions the history may be filled up with large number of records related to the communication and important records may be overwritten quite fast LB UART Log 6 back to List of setpoints Setpoint group Comms Settings Related FW 3 0 0 Range units...

Page 120: ...iption of Modbus protocol include some examples see in InteliGen Communication guide RS232 Mode 6 back to List of setpoints Setpoint group Comms Settings Related FW 3 0 0 Range units 19200 38400 57600 115200 bps Default value 38400 Step Comm object 24341 Related applications All Config level Standard Setpoint visibility Always Description The setpoint adjusts communication speed of the RS232 inter...

Page 121: ...up Comms Settings Related FW 3 0 0 Range units STANDARD MODBUS ECU LINK Default value STANDARD Step Comm object 24451 Related applications All Config level Standard Setpoint visibility Always Description Communication protocol selection STANDARD InteliDrive DriveConfig InteliMonitor Remote panel communication protocol MODBUS Modbus RTU protocol ECU LINK Connection to an electronic controlled engin...

Page 122: ...tep Comm object 11024 Related applications All Config level Standard Setpoint visibility Always Description This setpoint is used to enable disable evaluation of collisions of virtual shared peripherial modules A collision means that there is more than one source shared outputs module active on the CAN2 bus Note In certain situations multiple sites with bus tie breakers may need to have more share...

Page 123: ...nge units 30 1500 RPM Default value 350 Step 1 Comm object 9095 Related applications All Config level Standard Setpoint visibility Always Description Firing speed when controller stops cranking one of the engine running indications Note Under speed limit is fix 30 RPM Starting RPM 6 back to List of setpoints ...

Page 124: ...e Step Range and dimension depend on corresponding Analog input sensor characteristic Starting POil 6 back to List of setpoints Setpoint group Engine params Related FW 3 0 0 Range units 0 0 10 0 Bar Default value 10 0 Step 0 1 Comm object 10138 Related applications PRP Config level Standard Setpoint visibility Always Description Coolant pressure limit one of the engine running indications To activ...

Page 125: ...wise the Starting procedure is not activated Prestart Time 6 back to List of setpoints Setpoint group Engine params Related FW 3 0 0 Range units 1 200 s Default value 8 Step 1 Comm object 8234 Related applications All Config level Standard Setpoint visibility Always Description Amount of time the controller will crank the engine in an attempt to start MaxCrank Time 6 back to List of setpoints Setp...

Page 126: ...HRB only The setpoint is not followed if Sd Override is active crank attempts number is then unlimited in case of Blackout Start Together with request of unlimited start attempts was created LBI PrestartOverride activation means immediate transition from state Prestart to Cranking Same function was applied to second push of START button First press of START button activates state Prestart second p...

Page 127: ...Note 100 of Engine Values Requested Speed is the range between Engine params Idle RPM and Basic setting Nominal RPM Idle Offset 6 back to List of setpoints Setpoint group Engine params Related FW 3 0 0 Range units 0 600 s Default value 10 Step 1 Comm object 9097 Related applications All Config level Standard Setpoint visibility Always Description Idle time delay starts when RPM exceeds Starting RP...

Page 128: ...rTime 6 back to List of setpoints Setpoint group Engine params Related FW 3 0 0 Range units 1 4000 min Default value 1 Step 1 Comm object 8781 Related applications All Config level Standard Setpoint visibility Always Description Time interval between prelubrication cycles PrelubrTime page 128 Note To use Prelubrication configure Binary output Prelubrication at first Prelubrication is disabled in c...

Page 129: ...ams Related FW 3 0 0 Range units 0 600 s Default value 30 Step 1 Comm object 8258 Related applications All Config level Standard Setpoint visibility Always Description Runtime of unloaded engine to cool down engine before stopping Cooling Time 6 back to List of setpoints Setpoint group Engine params Related FW 3 0 0 Range units 0 600 s Default value 120 Step 1 Comm object 8662 Related applications...

Page 130: ...s All Config level Standard Setpoint visibility Always Description ENABLED The D terminal is used for both functions running engine detection and charge fail detection CHRGFAIL The D terminal is used for charge fail detection only DISABLED The D terminal is not used Note Alternator magnetization current is provided independently from the parameter setting D function 6 back to List of setpoints ...

Page 131: ...arams Stop Time timer if stop command is sent to an engine GAS Ignition is activated binary output Ignition is closed when RPM is over the 30 RPM fix value Gas valve binary output Gas is closed is opened 1 sec after Ignition output Gas output opens after stop command or in pause between repeated start If the gas engine is unsuccessful in starting the starter output will stay energized 25 longer in...

Page 132: ...inary output Clutch Connect opens this action deactivates loadsharing mode if it was activated before and Loadsharing ThrottlePos is set to Engine params FireAlarmSpeed value FireAlarmSpeed 6 back to List of setpoints Setpoint group Engine params Related FW 3 0 0 Range units ENABLED DISABLED Default value DISABLED Step Comm object 10098 Related applications All Config level Standard Setpoint visib...

Page 133: ...All Config level Standard Setpoint visibility Always Description Setpoint specifies Engine Values Speed Request when Engine params EnLocalSpeed ENABLED Setpoint can be changed as standard setpoint or by Fast edit function press Enter for 4 sec set value press Enter to confirm see Speed Request page 266 charts for PRP and AUX EME HRB modes Local Speed 6 back to List of setpoints ...

Page 134: ...Timeout 6 back to List of setpoints Setpoint group Engine protect Related FW 3 0 0 Range units 0 60 s Default value 10 Step 1 Comm object 10023 Related applications All Config level Standard Setpoint visibility Always Description This parameter adjusts delay after engine start when alarms configured as RunOnlyBlkDel1 i e running only group 1 are started to be evaluated The running only alarms are ...

Page 135: ...ty Always Description This parameter adjusts delay after engine start when alarms configured as RunOnlyBlkDel2 i e running only group 2 are started to be evaluated The running only alarms are not beeing evaluated while the engine is not running or then after start while the adjusted delay is running For details see drawing which is part of RunOnlyBlkDel3 page 136 description RunOnlyBlkDel2 6 back ...

Page 136: ...l3 i e running only group 3 are started to be evaluated The running only alarms are not beeing evaluated while the engine is not running or then after start while the adjusted delay is running Note Engine running state RPM Engine params Starting RPM or Analog input Oil Press Engine params Starting Poil or Analog input Coolant Press Engine params StartPCoolant PRP only or Active Binary input RunInd...

Page 137: ...riveConfig to BinInp delay 1 For details see BinInp Delay 3 page 138 description BinInp Delay 1 6 back to List of setpoints Setpoint group Engine protect Related FW 3 0 0 Range units 0 60 s Default value 5 Step 1 Comm object 10132 Related applications All Config level Standard Setpoint visibility Always Description Binary input protection is activated when input is closed for longer time than BinI...

Page 138: ...scription Binary input protection is activated when input is closed for longer time than BinInp delay 3 To use this filter binary input protection Delay must be configured in DriveConfig to BinInp delay 3 Note BinInp delay x is active only for Binary inputs configured as protection and it is related to protection only BinInp delay x does not affect optional logical function of an input BinInp Dela...

Page 139: ...tion is activated deactivated independent on engine running or not running state ForceBlockDel1 6 back to List of setpoints Setpoint group Engine protect Related FW 3 0 0 Range units 0 60 s Default value 0 Step 1 Comm object 10570 Related applications All Config level Standard Setpoint visibility Always Description Delay for Force block protection activation after binary input Force Block 2 is ope...

Page 140: ...nary input Force Block 3 is opened Protection deactivation is without delay Protection is activated deactivated independent on engine running or not running state ForceBlockDel3 6 back to List of setpoints Setpoint group Engine protect Related FW 3 0 0 Range units 0 200 Default value 110 Step 1 of Nominal RPM Comm object 8263 Related applications All Config level Standard Setpoint visibility Alway...

Page 141: ...0 Step 1 Comm object 10139 Related applications All Config level Standard Setpoint visibility Always Description Binary output Ready to load is closed if RPM MinLoadSpeed and engine is in Running state Use this output to enable disable connecting of engine load MinLoadSpeed is a condition to close BO Close Load when panel I 0 button is used to connect load to engine MinLoadSpeed 6 back to List of ...

Page 142: ...FW 3 0 0 Range units 0 600 s Default value 10 Step 1 Comm object 8383 Related applications All Config level Standard Setpoint visibility Always Description Delay for battery voltage alarms Batt Volt Del 6 back to List of setpoints Setpoint group Engine protect Related FW 3 0 0 Range units 0 0 100 0 Default value 20 0 Step 0 1 Comm object 9950 Related applications PRP Config level Standard Setpoint...

Page 143: ...unning Service alarm is indicated in Alarm list and History record is done when counter reaches zero Service time setpoint is initial counter value and it is gradually decrement when engine runs Note Once the service time has elapsed the Service time will have to be adjusted to non zero value to clear the alarm and begin a new countdown Service Time 6 back to List of setpoints Setpoint group Engin...

Page 144: ...racteristics Note The particular RPM dependent protection is fully disabled if both xxxIdlexxx and xxxNomxxx parameters are set to value 0 0 I e the protection is not activated even if measured value is negative e g when there is a wrong sensor calibration Setpoint group RPMdep Protect Related FW 3 0 0 Range units 0 0 10 0 Bar Default value 0 0 Step 0 1 Comm object 10140 Related applications PRP C...

Page 145: ...m object 10142 Related applications PRP Config level Standard Setpoint visibility Always Description Linear Shutdown characteristic is defined by two points for Idle RPM and Nominal RPM OPIdleRPMSd defines oil pressure shutdown level at idle speed For details see OilPrRPMdel page 146 description OPIdleRPMSd 6 back to List of setpoints Setpoint group RPMdep Protect Related FW 3 0 0 Range units 0 0 ...

Page 146: ... be linked with LAI Oil Press Note RPM dependent oil pressure protection is fix configured Protection block type Engine running only with RunOnlyBlkDel1 delay OilPrRPMdel 6 back to List of setpoints Setpoint group RPMdep Protect Related FW 3 0 0 Range units 0 0 10 0 Bar Default value 0 0 YES Step 0 1 Comm object 10144 Related applications PRP Config level Standard Setpoint visibility Always Descri...

Page 147: ... 1 Comm object 10146 Related applications PRP Config level Standard Setpoint visibility Always Description Linear Shutdown characteristic is defined by two points for Idle RPM and Nominal RPM CPIdleRPMSd defines coolant pressure shutdown level at idle speed For details see CoolPrRPMdel page 148 description CPIdleRPMSd 6 back to List of setpoints Setpoint group RPMdep Protect Related FW 3 0 0 Range...

Page 148: ...cription RPM dependent Coolant pressure protection delay Corresponding protection is activated when Coolant pressure is below limit for CoolPrRPMdel To activate RPM dependent coolant pressure protection any analog value has to be linked with LAI Coolant Press Note RPM dependent coolant pressure protection is fix configured Protection block type Engine running only with RunOnlyBlkDel1 delay CoolPrR...

Page 149: ...value 10 0 Step 0 1 Comm object 8713 Related applications PRP Config level Standard Setpoint visibility Always Description Relative Integration factor of the load sharing loop Load Int 6 back to List of setpoints Setpoint group Load sharing Related FW 3 0 0 Range units 0 1000 Default value 5 Step 1 Comm object 10136 Related applications PRP Config level Standard Setpoint visibility Always Descript...

Page 150: ...eliDrive DCU Marine 3 0 0 Global Guide 150 Setpoint group Load sharing Related FW 3 0 0 Range units 0 100 s Default value 5 Step 1 Comm object 10148 Related applications PRP Config level Standard RQSP Ramp ...

Page 151: ...er value after ramp specified by Loadsharing RQSP Ramp setpoint YES YES ThrottlePos Throttle position YES YES Engine values group Speed Request Speed request YES NO Image 8 1 Load sharing block diagram Note The maximal ThrottlePos difference between parallel operating engines due to Load sharing function is 1 5 ThrottlePos output request to EMS is switched to be equal to the Engine Values Speed re...

Page 152: ...liDrive DCU Marine 3 0 0 Global Guide 152 Setpoint group Load sharing Related FW 3 0 0 Range units 0 1000 Default value 5 Step 1 Comm object 10000 Related applications PRP Config level Standard ThrottlePos ...

Page 153: ...ions are met Actual Engine speed is in range specified by setpoints Loadsharing ClutchMinSpeed and ClutchMaxSpeed Logical Binary input Rem Clutch is active or I 0 front panel button is pressed There is loadsharing activation delay specified by setpoint Loadsharing Clutch Del to postpone loadsharing regulation after transient events after engine mechanical connection to gear box Note It is essentia...

Page 154: ...aring Related FW 3 0 0 Range units 0 0 60 0 s Default value 5 Step 0 1 Comm object 9949 Related applications PRP Config level Standard Setpoint visibility Always Description Time between the clutch is switched on off and the load sharing function is activated Clutch Del 6 back to List of setpoints ...

Page 155: ...0 corresponds to Idle speed Idle offset value 100 0 corresponds to Nominal speed ClutchMinSpeed 6 back to List of setpoints Setpoint group Load sharing Related FW 3 0 0 Range units ClutchMinSpeed 100 0 Default value 100 0 Step 0 1 Comm object 10097 Related applications PRP Config level Standard Setpoint visibility Always Description Clutch can be switched on if ClutchMinSpeed RPM ClutchMaxSpeed Li...

Page 156: ...inary input Back Up Speed is active and LAI Requested RPM reading via analog input is out of range sensor fail is detected Back Up Speed 6 back to List of setpoints Setpoint group Load sharing Related FW 3 0 0 Range units 0 600 s Default value 60 Step 1 Comm object 10102 Related applications PRP Config level Standard Setpoint visibility Always Description Engine clutch start protection Start fail ...

Page 157: ...NABLED Default value DISABLED Step Comm object 9921 Related applications PRP Config level Standard Setpoint visibility Always Description Enables Wrn OthrCommEr warning message when no other unit is recognized on the CAN bus Binary output OthrCommEr is closed in this case DetectOtherCAN 6 back to List of setpoints ...

Page 158: ...roup Analog Inputs Related FW 3 0 0 Range units 32767 32767 Default value 0 Step Comm object 8407 Related applications Config level Standard Setpoint visibility Always Description Adjustable offset for AIN2 for calibrating purposes AIN2 Offset 6 back to List of setpoints Setpoint group Analog Inputs Related FW 3 0 0 Range units 32767 32767 Default value 0 Step Comm object 8467 Related applications...

Page 159: ...alog Inputs Related FW 3 0 0 Range units 32767 32767 Default value 0 Step Comm object 8794 Related applications Config level Standard Setpoint visibility Always Description Adjustable offset for AIN5s for calibrating purposes AIN5 Offset 6 back to List of setpoints Setpoint group Analog Inputs Related FW 3 0 0 Range units 32767 32767 Default value 0 Step Comm object 8795 Related applications Confi...

Page 160: ...t visibility Always Description Adjustable offset for AIN7 for calibrating purposes AIN7 Offset 6 back to List of setpoints Setpoint group Analog Inputs Related FW 3 0 0 Range units 32767 32767 Default value 0 Step Comm object 11599 Related applications Config level Standard Setpoint visibility Always Description Adjustable offset for AIN8 for calibrating purposes AIN8 Offset 6 back to List of set...

Page 161: ...0 Range units DISABLED ENABLED Default value DISABLED Step Comm object 8484 Related applications All Config level Standard Setpoint visibility Always Description Enables or disables active calls to selected phone or mobile numbers when a Shutdown alarm occurs Shut Down Call 6 back to List of setpoints Setpoint group Act Calls SMS Related FW 3 0 0 Range units DISABLED ENABLED Default value DISABLED...

Page 162: ... connected EML SMS Channel sends short e mail with SMS like content Only when InternetBridge NT is connected Email contains header with serial number and application info Alarm list 20 History records reason date time Example of EML SMS AL Sd Water Temp Wrn Water Temp Emerg Stop ActCallCH1Fail Note Both SMS and E MAIL active call types are supported in conjunction with InternetBridge NT if cellula...

Page 163: ... connected EML SMS Channel sends short e mail with SMS like content Only when InternetBridge NT is connected Email contains header with serial number and application info Alarm list 20 History records reason date time Example of EML SMS AL Sd Water Temp Wrn Water Temp Emerg Stop ActCallCH1Fail Note Both SMS and E MAIL active call types are supported in conjunction with InternetBridge NT if cellula...

Page 164: ...ange units Default value 0 Step Comm object 9597 Related applications All Config level Standard Setpoint visibility Always Description Address for channel 1 active call Each above message type has either phone number or e mail address associated with it AcallCH1 Addr 6 back to List of setpoints ...

Page 165: ...NT isc EML SMS Channel sends short e mail with SMS like content Only when InternetBridge NT is connected Email contains header with serial number and application info Alarm list 20 History records reason date time Example of EML SMS AL Sd Water Temp Wrn Water Temp Emerg Stop ActCallCH1Fail Note Both SMS and E MAIL active call types are supported in conjunction with InternetBridge NT if cellular in...

Page 166: ...99 Related applications All Config level Standard Setpoint visibility Always Description Address for channel 3 active call Each above message type has either phone number or e mail address associated with it AcallCH3 Addr 6 back to List of setpoints Setpoint group Act Calls SMS Related FW 3 0 0 Range units 1 30 Default value 3 Step 1 Comm object 24512 Related applications All Config level Standard...

Page 167: ...ll Config level Standard Setpoint visibility Always Description Setpoint specifies number of attempts to open Active call connection when phone line is engaged Note Timeout for connection is 90 sec and after 120 sec controller starts the next attempt Incoming calls are blocked when controller is trying to send active call message A C Multiplier 6 back to List of setpoints ...

Page 168: ...D MM YY Default value 8 6 2006 Step Comm object 24553 Related applications All Config level Standard Setpoint visibility Always Description Actual date adjustment Date 6 back to List of setpoints Setpoint group Date Time Related FW 3 0 0 Range units 0 240 min Default value 1 Step 1 Comm object 8979 Related applications All Config level Standard Setpoint visibility Always Description The setpoint a...

Page 169: ...here SUMMER The automatic change is enabled the current season is summer and the controller is located in the northern hemisphere WINTER S The automatic change is enabled the current season is winter and the controller is located in the southern hemisphere SUMMER S The automatic change is enabled the current season is summer and the controller is located in the southern hemisphere SummerTimeMod 6 ...

Page 170: ...ck to List of setpoints Setpoint group SCM unit Related FW 3 0 0 Range units 0 500 Default value 0 Step 1 Comm object 10903 Related applications All Config level Standard Setpoint visibility Always Description Conversion constant number of pulses for one RPM for ID SCM RPM2 frequency input SCM Freq2 value Frequency range max 8 kHz FreqRate2 6 back to List of setpoints Setpoint group SCM unit Relat...

Page 171: ...ual water flow in liters or cubic meters per minute set FreqRate 10 when sensor gives 10 pulses per liter or cubic meters Example To measure total water consumption in liters or cubic meters set TransferRate 100 when sensor gives 100 pulses per 1liter or cubic meter TransferRate2 6 back to List of setpoints DetCon20 Setpoint group DetCon20 Related FW 3 0 0 Range units 0 0 25 4 s Default value 1 0 ...

Page 172: ...10299 Related applications All Config level Standard Setpoint visibility DetCon20 support configured Description Ignition reduction limit is knocking value above which the engine is considered to be knocking If the value is exceeded DetCon20 binary output ENGINE KNOCKING is activated and the values assigned to the timing reduction are altered IgnRedLimit 6 back to List of setpoints Setpoint group ...

Page 173: ...t value 40 0 YES Step 0 1 Comm object 10301 Related applications All Config level Standard Setpoint visibility DetCon20 support configured Description Timing reduction gain influences rate at which timing reduction signal analog output is amplified when knocking is detected TimingRedGain 6 back to List of setpoints ...

Page 174: ...ed to any physical input ID DCU MARINE binary inputs Remote Start Remote Stop Rem Start Stop are not active in LOC local mode Note Minimal input pulse duration is 120 ms to be detected as valid binary inputs sampling rate is 100 ms Adjustable delay can be configured to any binary input when is used as a protection Standard 0 5 sec or one of BinInp delay 1 2 3 that can be adjusted by corresponding ...

Page 175: ...ocking4 184 StartBlocking5 184 Load Blocking 184 RunIndication1 185 RunIndication2 185 RunIndication3 185 Nominal Speed 186 Loaded 186 Emerg Manual 186 EnClutchStart 186 Sd Override 187 Speed Down 187 Speed Up 188 ECU FltReset 188 BI Droop 189 BI Second RPM 189 BI Idle 189 Rem Start Stop 189 PrestartOvrd 190 ClutchBlocking 190 ModeL Button 190 ModeR Button 190 Page Button 190 Enter Button 191 Up B...

Page 176: ...lt reset screen sensitive Horn reset buttons are still active It is possible to list Values Setpoints and History Binary inputs function is without change Active Access lock is indicated by L in the upper right corner of controller screen Note Access Lock does not protect Setpoints change Mode change and START STOP commands from InteliMonitor direct or modem To avoid unqualified changes of the sel...

Page 177: ...Device Command Access lock Remote lock LOC Local mode ID DCU MARINE panel START N Y Y STOP N Y Y FLT RES Y Y Y HORN RES Y Y Y Setpoint change N Y Y Mode change N Y Y ID DCU MARINE Bin Inputs Remote start Y Y N Remote stop Y Y N Remote OFF Y Y N External modules Bin Inputs start stop Y Y N Remote OFF Y Y N Remote HBR Y Y N RS232 or CAN2 STOP Y N N FLT RES Y N N HORN RES Y N N Setpoint change Y N N ...

Page 178: ...tored in non volatile memory Note Both backlight levels are default from production set to maximum Low Brightness 6 back to List of LBI Related FW 3 0 0 Related applications All Comm object 16 Description Active input blocks protections that are configured as Force Block 1 Prot block type Corresponding setpoint is ForceBlockDel1 Force Block 1 6 back to List of LBI Related FW 3 0 0 Related applicat...

Page 179: ...and back to previous mode after is opened Input is not active in LOC Local mode Active binary input Remote OFF is indicated by L character in the right upper corner on ID DCU MARINE screen Note Remote OFF will switch controller to OFF mode even if the Access Lock or Remote Lock is active or Controller mode is password protected Remote OFF 6 back to List of LBI Related FW 3 0 0 Related applications...

Page 180: ...and use a NC switch IMPORTANT This is a software function only It can be extended by a hard wired emergency stop function which means disconnecting power supply from the controller outputs EmergencyStop1 6 back to List of LBI Related FW 3 0 0 Related applications All Comm object 928 Description If the input is activated engine shutdown is immediately performed However the controller behavior is sl...

Page 181: ...tart button Remote Start 6 back to List of LBI Related FW 3 0 0 Related applications All Comm object 157 Description Engine edge sensitive stop request The first edge changes engine state from running to cooling the second edge stops engine skip the rest of cooling Binary input is inactive in LOC Local mode Remote Stop signal is equivalent to ID DCU MARINE front panel Stop button Note Binary input...

Page 182: ...AUX EME CMB EME CMB HRB PRP not available PRP other modes not available AUX EME PRP CMB EME CMB HRB LOC Inactive in MODE LOC LOC LOC all time active Number of starting attempts 1 x Engine params Crank Attempts Engine params Crank Attempts 1 x Engine starting signals Remote Stop Panel STOP button 1 sec holding time for Stop button activation Input sensitive Edge sensitive 2 nd edge skips Cooling Ed...

Page 183: ...ts RemRepStart PRP only 6 back to List of LBI Related FW 3 0 0 Related applications All Comm object 160 Description If active clutch is disconnected and Loadsharing ThrottlePos is set to Engine params FireAlarmSpeed the ThrottlePos value change is influenced by ramp specified by Loadsharing RQSP Ramp Fire Speed 6 back to List of LBI Related FW 3 0 0 Related applications PRP Comm object 183 Descrip...

Page 184: ...6 back to List of LBI Related FW 3 0 0 Related applications All Comm object 582 Description OR logical function of all StartBlocking Logical Binary inputs forces controller NotReady state i e disables engine start It is active in LOC Local mode as well StartBlocking4 6 back to List of LBI Related FW 3 0 0 Related applications All Comm object 583 Description OR logical function of all StartBlocking...

Page 185: ...cation e g via Oil pressure contact Active Running indication blocks engine start to avoid starter damage Engine running state RPM Engine params Starting RPM or Analog input Oil pressure Engine params Starting Poil or Active Binary input RunIndication1 or Active Binary input RunIndication2 or Active Binary input RunIndication3 RunIndication2 6 back to List of LBI Related FW 3 0 0 Related applicati...

Page 186: ...ailure which does not allow the gen set to be controlled by the controller but the gen set itself is stays operational The controller behaves following way Shows the text EmergMan in the engine status on the main screen Stops all functions regarding the engine control deactivates all outputs related to it except Fuel Solenoid Stop Fail alarm is not being evaluated and Stop Solenoid is not activate...

Page 187: ...ed when the binary input is closed Speed Down has higher priority when both Up and Down inputs are active RPM inc dec rate is defined by setpoint Engine params BI Speed ramp Engine speed can be set by Logical Analog Input Requested RPM or by BI Speed Up and Speed Down Following Speed Request initialization is valid when Analog input Requested RPM is not configured Speed Request Idle 0 0 Inputs are...

Page 188: ...Engine Values page 267 and page 267 modes The Binary inputs SpeedUp and SpeedDown ramp function is for the 0 6 sec constant 0 4 s and does not depend on Engine params SpeedRamp setting This function enables fine setting of Engine speed to specific like 1500 RPM value Dual rate ramp Note Minimal Speed Up and Speed Down pulse duration is 110ms to be accepted by controller Speed Up 6 back to List of ...

Page 189: ...t Idle Nominal that can be configured as J1939 output to change ECU mode Input is active only when Basic setting Idle Nominal BIN INPUT BI Idle 6 back to List of LBI Related FW 3 0 0 Related applications All Comm object 172 Description Rem Start Stop is level signal that activates engine start when closed and stop after is opened It is inactive in LOC Local mode It is not possible to stop engine b...

Page 190: ...omm object 182 Description ClutchBlocking can block the LBO Clutch Connect Active input is indicated in Alarm list as Clutch Blocking message ClutchBlocking 6 back to List of LBI Related FW 3 0 0 Related applications All Comm object 200 Description Input simulates the panel Mode button ModeL Button 6 back to List of LBI Related FW 3 0 0 Related applications All Comm object 201 Description Input si...

Page 191: ...utton 6 back to List of LBI Related FW 3 0 0 Related applications All Comm object 205 Description Input simulates the panel button Down Button 6 back to List of LBI Related FW 3 0 0 Related applications All Comm object 269 Description Input controls ECU Diagnostic functionality in case of setting ECU Diag EXTERNAL ECU DiagBlck 6 back to List of LBI Related FW 3 0 0 Related applications All Comm ob...

Page 192: ...ption Rising edge forces to fill register Statistics Memo1 by Logical Analog Input Memory1 actual value Memo1 Statistics value can be set or resetted by InteliMonitor command Memo1 Trigger 6 back to List of LBI Related FW 3 0 0 Related applications All Comm object 585 Description Rising edge forces to fill register Statistics Memo2 by Logical Analog Input Memory2 actual value Memo2 Statistics valu...

Page 193: ...Logical binary inputs Mask 1 4 can be used to define any custom condition for this swapping function User Mask 1 6 back to List of LBI Related FW 3 0 0 Related applications All Comm object 568 Description This input allows user to activate chosen function in ScreenEditor tool inside DriveConfig for particular screen instrument User may choose from the following functions None Show Hide No action r...

Page 194: ...ary inputs Mask 1 4 can be used to define any custom condition for this swapping function User Mask 3 6 back to List of LBI Related FW 3 0 0 Related applications All Comm object 570 Description This input allows user to activate chosen function in ScreenEditor tool inside DriveConfig for particular screen instrument User may choose from the following functions None Show Hide No action regarding th...

Page 195: ...cations All Comm object 722 Description Rising edge of this input will provide reset of controller processor Watchdog test 6 back to List of LBI Binary inputs from J193 configuration Binary inputs protection Property Function line is free no logical function is usually selected ...

Page 196: ...InteliDrive DCU Marine 3 0 0 Global Guide 196 8 1 4 Binary outputs Depending on Modules configuration there are exist more groups of binary items that can be configured to any physical binary output ...

Page 197: ...ng Alarm 210 RdyForRemStart 211 ECU PowerRelay 211 StartButtEcho 211 StopButtEcho 212 FltResButtEcho 212 HrnResButtEcho 212 ClutchButtEcho 212 HrnResBtToggle 213 MalfunctLamp 213 ActLoadShar 213 AirFlaps 213 MCU AckButton 214 User Button 1 214 User Button 2 214 User Button 3 214 User Button 4 214 User Button 5 215 User Button 6 215 User Button 7 215 User Button 8 215 User Button 9 215 User Button ...

Page 198: ...229 PLC Message 9 229 PLC Message 10 229 PLC Message 11 229 PLC Message 12 229 PLC Message 13 229 PLC Message 14 230 PLC Message 15 230 PLC Message 16 230 Emergency Stop 230 Engine RPM 230 Overload 230 OthrCommEr 231 ChrgAlternFail 231 Stop Fail 231 Overspeed 231 Underspeed 231 Pickup Fail 232 Battery Flat 232 Battery Volt 232 WrnService Time 232 Not Lubricated 232 Start Fail 233 OP RPMdep 233 CP ...

Page 199: ...to overfill with soot because the system is unable to undertake an automatic active regeneration It starts flashing when the DPF is nearly full engine power may be reduced DPF Lamp 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 1373 Description Indicates High Exhaust System Temperature HEST It may be active during DPF regeneration to indicate higher than normal exhaust...

Page 200: ... 0 0 Related applications All Comm object 3 Description The output closes when any Warning alarm is active Output opens when all Wrn alarms disappear and Fault reset is pressed no Wrn alarm in Alarm list Common Wrn 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 4 Description The output closes when any Shut down alarm is active Output opens when all Sd alarms disappear ...

Page 201: ...ject 17 Description TThe output is closed in controller OFF mode OFF Mode 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 1831 Description Active signal indicates that DPF Diesel Particulate Filter is starting to overfill with soot because the system is unable to undertake an automatic active regeneration It starts flashing when the DPF is nearly full engine power may b...

Page 202: ...pplications All Comm object 260 Description CPU indication output is closed when CPU is ready CPU Ready 6 back to List of LBO Related FW 3 0 0 Related applications PRP Comm object 261 Description Output is closed if Binary input Rem Clutch is active or controller front panel I 0 button is pressed and actual engine RPM is between ClutchMinSpeed and ClutchMaxSpeed Output stays closed even if the RPM...

Page 203: ...closes during engine start after Idle time setpoint elapses The output opens again after Cooling time is finished The opposite logic output Nominal Idle is available as well Note Connect Binary output Idle Nominal to electronic speed governor to switch the speed opened IDLE closed RATED Idle Nominal 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 1373 Description Indica...

Page 204: ...ll Comm object 262 Description Engine ready for start indication no start blocking alarm is active Output is active in LOC Local mode as well even if can t be started by binary inputs Ready To Start 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 67 Description Output closes if the engine is in Running state and can be loaded Opens in Cooling state Active only if RPM Mi...

Page 205: ...e during cranking pause and after stop of the engine RPM 0 Ignition 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 264 Description 1 sec fix pulse prior to transfer from Running to Cooling state Unload 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 74 Description Closes in cooling state opens after engine stop Cooling 6 back to List of LBO ...

Page 206: ...on Output is closed when panel 0 1 On Off button is pressed or Binary input Remote On Off is closed and engine RPM is over Engine protection MinLoadSpeed Output opens when RPM is bellow MinLoadSpeed Close load can t be opened by button when Binary input Remote On Off level sensitive is closed Function can be blocked by binary input Load blocking Close Load 6 back to List of LBO Related FW 3 0 0 Re...

Page 207: ...ry input BI Secondr RPM is closed This logical output Source can be configured to corresponding J1939 output e g Frequency Select in Volvo IndustrialD12 Aux see an example below Function of Speed select implemented in InteliDrive DCU has no influence on Speed Request by default setting Logical binary output Second RPM Sw is normally used to select the rated speed where the exact settings depend on...

Page 208: ...es not communicate 2s timeout Comm BIN Fail 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 271 Description Communication warning fail when any Analog output module address does not communicate 2s timeout Comm AOUT Fail 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 272 Description Communication warning fail when any Binary output module add...

Page 209: ...t least one alarm is active Output opens when Alarm list is empty Alarm Blink 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 276 Description The output is closed when setpoint Basic setting Idle Nominal NOMINAL or Idle Nominal BIN INPUT and corresponding Binary input BI Nominal is closed This logical output Source can be configured to corresponding J1939 output e g Idl...

Page 210: ...rt Stop Timer is active in all controller modes include OFF mode Timer Active 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 278 Description It follows the panel Red LED Starts blink after any Wrn Sd Alarm is activated light after Fault reset disappear after Fault reset when no alarm is active Alarm BlinkAct 6 back to List of LBO Related FW 3 0 0 Related applications A...

Page 211: ... output also influences evaluation of communication failure with ECU and related FLS alarms from analog inputs read from the ECU If the output is configured which means configured on physical binary output or VBOUT output the issuing of communication error is blocked during Prestart and Stopping procedure as shown in the picture Note The input must be configured on physical binary output or VBOUT ...

Page 212: ...button is pressed The pulse is generated only in case that Alarm List screen is displayed on the controller i e in the time of possibility to acknowledge alarms FltResButtEcho 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 284 Description 1 sec pulse is generated after panel Horn reset button is pressed HrnResButtEcho 6 back to List of LBO Related FW 3 0 0 Related appl...

Page 213: ...Monitor Modbus Modem as well HrnResBtToggle 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 1832 Description Indicates that emissions related engine fault code is active MalfunctLamp 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 449 Description Indication of active Load sharing ActLoadShar 6 back to List of LBO Related FW 3 0 0 Related appl...

Page 214: ... Related FW 3 0 0 Related applications All Comm object 727 Description InteliVision function buttons can be assigned to these LBOs User Button 1 16 The configuration of button s functionality is done via Screen Editor feature in DriveConfig PC application User Button 2 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 728 Description InteliVision function buttons can be a...

Page 215: ...ed applications All Comm object 752 Description InteliVision function buttons can be assigned to these LBOs User Button 1 16 The configuration of button s functionality is done via Screen Editor feature in DriveConfig PC application User Button 7 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 1087 Description InteliVision function buttons can be assigned to these LBOs ...

Page 216: ...ed applications All Comm object 1091 Description InteliVision function buttons can be assigned to these LBOs User Button 1 16 The configuration of button s functionality is done via Screen Editor feature in DriveConfig PC application User Button 12 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 1092 Description InteliVision function buttons can be assigned to these LBO...

Page 217: ...onfiguration of button s functionality is done via Screen Editor feature in DriveConfig PC application User Button 16 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 960 Description Indicates that automatic DPF filter regeneration is inhibited using REG INHIB PAGE 181 RegenInhibit 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 1834 Descripti...

Page 218: ... Comm object 142 Description Those eight LBOs can be handled from InteliMonitor Remote switch window This way can operator directly handle controller binary outputs or other e g PLC functions RemoteControl2 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 143 Description Those eight LBOs can be handled from InteliMonitor Remote switch window This way can operator directl...

Page 219: ... way can operator directly handle controller binary outputs or other e g PLC functions RemoteControl6 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 147 Description Those eight LBOs can be handled from InteliMonitor Remote switch window This way can operator directly handle controller binary outputs or other e g PLC functions RemoteControl7 6 back to List of LBO Relate...

Page 220: ...te EmStop RPU Indication of ID RPU Emergency stop input state Related FW 3 0 0 Related applications RPU Comm object 10213 Description Binary output Fuel solenoid FS status when output is opened 0 OK 1 Fail Broken wire BW Table 8 1 FS Status Note The High Current is indicated if output current is over 1A approx FS Status 6 back to List of LBO Related FW 3 0 0 Related applications RPU Comm object 10...

Page 221: ...ack to List of LBO Related FW 3 0 0 Related applications RPU Comm object 10213 Description Status of ID RPU Fuel solenoid and Stop solenoid power supply terminal Active when Power supply is NOT connected BinOut Power 6 back to List of LBO Related FW 3 0 0 Related applications RPU Comm object 10213 Description Indicates that system is switched to Battery B Battery Fail 6 back to List of LBO Related...

Page 222: ...d FW 3 0 0 Related applications RPU Comm object 10213 Description ID RPU watchdog timer is over ID DCU MARINE fail when closed Note Fuel and Stop solenoid Broken wire indications are available in the list of Prg states RPU Watchdog 6 back to List of LBO ...

Page 223: ...6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 1998 Description J1939 communication fail indication ECU1 Comm Fail 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 1999 Description J1939 communication fail indication ECU2 Comm Fail 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 2000 Description J1939 communication...

Page 224: ...lated applications All Comm object 2004 Description J1939 communication fail indication ECU7 Comm Fail 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 2005 Description J1939 communication fail indication ECU8 Comm Fail 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 2006 Description J1939 communication fail indication ECU10 Comm Fail 6 back t...

Page 225: ...ted applications All Comm object 2010 Description J1939 communication fail indication ECU13 Comm Fail 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 2011 Description J1939 communication fail indication ECU14 Comm Fail 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 2012 Description J1939 communication fail indication ECU15 Comm Fail 6 back t...

Page 226: ...m object 303 Description Output is closed when at least one item is in ECU Alarm list ECU AlarmList 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 185 Description Universal states 1 to Universal states 7 indication See Universal states page 31 description UnivState 1 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 186 Description Universal s...

Page 227: ...escription Universal states 1 to Universal states 7 indication See Universal states page 31 description UnivState 6 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 191 Description Universal states 1 to Universal states 7 indication See Universal states page 31 description UnivState 7 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object Description...

Page 228: ...osed while the alarm generated by the PLC block Force Prot is present in the alarm list PLC Message 4 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 372 Description The output is closed while the alarm generated by the PLC block Force Prot is present in the alarm list PLC Message 5 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 373 Descript...

Page 229: ...ed while the alarm generated by the PLC block Force Prot is present in the alarm list PLC Message 10 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 532 Description The output is closed while the alarm generated by the PLC block Force Prot is present in the alarm list PLC Message 11 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 533 Descript...

Page 230: ...applications All Comm object 793 Description The output is closed while the alarm generated by the PLC block Force Prot is present in the alarm list PLC Message 16 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 260 Description Indication of Emergency Stop input Emergency Stop 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object Description Engine...

Page 231: ... cranking Starting RPM StartingPOil and D function when ENABLED Starter goes off when any of these conditions becomes valid ChrgAlternFail 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object Description Engine stop fail indication Stop fail engine does not reach 0 RPM after stop command within Engine params Stop time Stop Fail 6 back to List of LBO Related FW 3 0 0 Related ...

Page 232: ...0 Related applications All Comm object 1293 Description Indication when battery voltage ID DCU MARINE power supply is out of Engine protect Batt V and Batt V limits Battery Volt 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object Description Output is closed when Service time count down 0 Note History record and Alarm list indication is activated as well WrnService Time 6 b...

Page 233: ...elated applications All Comm object Description Out of Cooling pressure RPM dependent limit indication CP RPMdep 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object Description It is closed when the battery A voltage of RPU is out of limits Engine protection Batt V Batt V Batt V del Battery A volt 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object D...

Page 234: ...was switched power supply to the battery B SwitchToBatt B 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object Description Start blocking indication Start Blocking 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object Description Clutch blocking indication ClutchBlocking 6 back to List of LBO ...

Page 235: ...e DCU Marine 3 0 0 Global Guide 235 Source Ana protections List of Analog inputs protection indication is dynamic Any protection configured e g on Analog input appears in Source Ana protection Binary output list ...

Page 236: ...InteliDrive DCU Marine 3 0 0 Global Guide 236 Source Bin protections List of Binary inputs protection indication is dynamic Any protection configured on Binary input appears in Source Bin protection ...

Page 237: ...ine 3 0 0 Global Guide 237 Source Binary Inputs CU Binary CU list contains all ID DCU MARINE binary inputs that can be configured to Binary outputs This source contains binary inputs physical states no protection activity ...

Page 238: ...ID RPU Shut down inputs state that can be configured to Binary outputs RPU SD 1 Indication of ID RPU Shut down 1 input state RPU SD 2 Indication of ID RPU Shut down 2 input state RPU SD 3 Indication of ID RPU Shut down 3 input state RPU SD 4 Indication of ID RPU Shut down 4 input state RPU SD 5 Indication of ID RPU Shut down 5 input state EmStop RPU Indication of ID RPU Emergency stop input state ...

Page 239: ...al Guide 239 Source Binary Inputs List depend on modules configuration contains all Extension modules binary inputs that can be configured to any Binary outputs This source contains binary inputs physical states no protection activity ...

Page 240: ...it indication OilTemp Oil temperature out of limit indication CoolantTemp Coolant temperature out of limit indication Coolant Level Coolant level out of limit indication Related FW 3 0 0 Related applications All Comm object 67 Description Engine running state indication Running 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object 779 Description Engine overspeed indication O...

Page 241: ...0 Related applications All Comm object 435 Description Oil temperature out of limit indication OilTemp 6 back to List of LBO Related FW 3 0 0 Related applications All Comm object Description Coolant level out of limit indication CoolantLevel 6 back to List of LBO ...

Page 242: ...InteliDrive DCU Marine 3 0 0 Global Guide 242 Binary output to J1939 configuration Source Value 8 1 5 Analog Inputs ...

Page 243: ...crAna2 248 Memory1 249 Memory2 250 Cold Temp 1 250 Cold Temp 2 251 Cold Temp 3 251 Cold Temp 4 251 Cyl Temp 1 252 Cyl Temp 2 252 Cyl Temp 3 252 Cyl Temp 4 252 Cyl Temp 5 252 Cyl Temp 6 252 Cyl Temp 7 253 Cyl Temp 8 253 Cyl Temp 9 253 Cyl Temp 10 253 Cyl Temp 11 253 Cyl Temp 12 253 Cyl Temp 13 254 Cyl Temp 14 254 Cyl Temp 15 254 Cyl Temp 16 254 6 back to Controller objects InteliDrive DCU Marine 3 ...

Page 244: ... 9 Description Engine oil pressure which is displayed at the first controller screen Note Configure Oil Press logical analog input LAI card in DriveConfig to display the value at the first controller screen Oil Press 6 back to List of LAI Related FW 3 0 0 Related applications All Comm object 67 Description Engine coolant temperature which is displayed at the first controller screen Note Configure ...

Page 245: ... FW 3 0 0 Related applications PRP Comm object 69 Description Actual engine torque in received from J1939 Engine Torque PRP only 6 back to List of LAI Related FW 3 0 0 Related applications All Comm object 82 Description There are two cumulative Statistics registers values TripCons and DayCons Those statistic values increment value based on sampling of Logical Analog Input Fuel ConsAct LAI can be s...

Page 246: ... input for engine fuel consumption value L h which is used for MomAvgFlCon L page 282 calculation FuelConsump 6 back to List of LAI Related FW 3 0 0 Related applications All Comm object 117 Description Analog input for boat speed value kts which is used for MomAvgFlCon L page 282 calculation BoatSpeed 6 back to List of LAI ...

Page 247: ...from AIN3 AirTemp1 instead OilPress the first position and AIN4 AirTemp2 instead CoolTemp value a Select AIN3 Property Function MainScrAna1 b Select AIN4 Property Function MainScrAna2 c Create new language in DriveConfig Languages based on English d Rename in DriveConfig Translator Other texts text OilPress to AirTemp1 in the newly created language e Rename in DriveConfig Translator Other texts te...

Page 248: ...from AIN3 AirTemp1 instead OilPress the first position and AIN4 AirTemp2 instead CoolTemp value a Select AIN3 Property Function MainScrAna1 b Select AIN4 Property Function MainScrAna2 c Create new language in DriveConfig Languages based on English d Rename in DriveConfig Translator Other texts text OilPress to AirTemp1 in the newly created language e Rename in DriveConfig Translator Other texts te...

Page 249: ...e are two Statistics registers Memo1 and Memo2 Those statistic values are based on Logical Analog Input Memory1 or Memory2 value in the time of Logical Binary input Memo1 Trigger or Memo2 Trigger rising edge Both statistics values is possible to modify in InteliMonitor Set Statistics command Memory1 6 back to List of LAI ...

Page 250: ...escription If there is an additional terminal board between a thermocouple sensor and the IS AIN8 TC module and there is a significant temperature difference between this terminal board and the module it is necessary to measure the temperature at this terminal board and use this temperature for the thermocouple compensation instead of the internal temperature of the module Cold Temp 1 Logical Anal...

Page 251: ...e it is necessary to measure the temperature at this terminal board and use this temperature for the thermocouple compensation instead of the internal temperature of the module Cold Temp 1 Logical Analog input is intended for measurement of this thermocouple compensation temperature for the IS AIN8 TC module with index 1 Cold Temp 2 corresponds to IS AIN8 TC module with index 2 etc Note Thermocoup...

Page 252: ...ons All Comm object 19 Description Analog inputs for engine Cylinder temperature measuring Cyl Temp 3 6 back to List of LAI Related FW 3 0 0 Related applications All Comm object 20 Description Analog inputs for engine Cylinder temperature measuring Cyl Temp 4 6 back to List of LAI Related FW 3 0 0 Related applications All Comm object 21 Description Analog inputs for engine Cylinder temperature mea...

Page 253: ...ns All Comm object 25 Description Analog inputs for engine Cylinder temperature measuring Cyl Temp 9 6 back to List of LAI Related FW 3 0 0 Related applications All Comm object 26 Description Analog inputs for engine Cylinder temperature measuring Cyl Temp 10 6 back to List of LAI Related FW 3 0 0 Related applications All Comm object 27 Description Analog inputs for engine Cylinder temperature mea...

Page 254: ...ns All Comm object 30 Description Analog inputs for engine Cylinder temperature measuring Cyl Temp 14 6 back to List of LAI Related FW 3 0 0 Related applications All Comm object 31 Description Analog inputs for engine Cylinder temperature measuring Cyl Temp 15 6 back to List of LAI Related FW 3 0 0 Related applications All Comm object 32 Description Analog inputs for engine Cylinder temperature me...

Page 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...

Page 256: ... 256 Analog inputs protection Three level protection configuration 1 Switch to I O analog inputs e g ID AIN8 2 Switch to Expert mode 3 Configure standard two level protection Expert field is now empty This field is visible in Expert mode only ...

Page 257: ...igured protection are now visible in Expert field and corresponding limits as well 5 Add the third protection button and edit Property e g Wrn Under Any protection limit delay can be set to Constant then value is fixed specified in line below and can not be changed by customer not included in setpoint list or ...

Page 258: ...ive DCU Marine 3 0 0 Global Guide 258 In example above there is Wrn limit type set to Const 60 There is visible setpoint corresponding to Wrn Over protection It is possible to change limit name value and limits ...

Page 259: ...obal Guide 259 Use button to add new limit for the third Wrn Under protection Name Limit3 can be changed Limit and Delay type must be in this case set to Setpoint Use button to add Delay setpoint and set change name value and limits ...

Page 260: ...otection on BO 1 Select free universal state for selected protection Note Configure this UnivState to some Binary output and modify Bin output Name Oil pressure and Water temperature on the first ID controller screen indication 1 Reading from ID DCU MARINE analog inputs ...

Page 261: ...InteliDrive DCU Marine 3 0 0 Global Guide 261 2 Reading from J1939 logical function Please note that Protections can be configured as well ...

Page 262: ...ndication Broken wire detection Shutdown BW Shut down Broken wire detection Warning Fls Warning is activated in the case of sensor fail as well Shutdown Fls Shut down is activated in the case of sensor fail as well Sd override This protection stays active in the case of Sd override is activated Alarm only Only Alarm list indication disappear without confirmation HistRecOnly History record only Pro...

Page 263: ...AIN CU 6 271 AIN CU 7 272 AIN CU 8 272 Group of values Binary CU ID BIN 273 ID BOUT 273 LogBout 4 274 Group of values Log Bout LogBout1 274 LogBout 2 274 LogBout 3 274 LogBout 6 275 LogBout 7 275 RemoteControl 275 Group of values Info Engine State 276 PasswordDecode 276 Build date 276 SW version 276 Application 277 SW Branch 277 Mode ID 277 Timer Text 277 Timer Val 277 ECU Alarms 1 278 ECU Alarms ...

Page 264: ...s Related FW 3 0 0 Resolution units 1 RPM Comm object 11401 Related applications All Description Filtered current engine speed for nice displaying without nozzle oscillations Note limit is defined by the value of the communication object of specified number EngRPMfiltered 6 back to List of values Value group Basic settings Related FW 3 0 0 Resolution units 1 Comm object 10135 Related applications ...

Page 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...

Page 266: ...InteliDrive DCU Marine 3 0 0 Global Guide 266 Value group Engine values Related FW 3 0 0 Resolution units 1 Comm object 10137 Related applications All Speed Request ...

Page 267: ...U Marine 3 0 0 Global Guide 267 Description Internal Speed Request value which can be used to control engine speed See following flow charts how the Speed Request value is generated in case of PRP or AUX EME HRB mode ...

Page 268: ...mm object 10006 Related applications All Description application PROP conversion 0 0 0 3 NominalRPM 100 0 1 1 NominalRPM application AUX CMB EME conversion 0 0 0 9 NominalRPM 100 0 1 1 NominalRPM In the case of sensor fail out of range is Sped request 0 for PRP and 50 Nominal RPM for AUX configuration SpeedReq RPM 6 back to List of values ...

Page 269: ...6 back to List of values Value group Engine values Related FW 3 0 0 Resolution units 1 C Comm object 10527 Related applications All Description Detected minimal temperature value from Logical Analog inputs Cyl Temp 1 Cyl Temp 16 T Cyl Min 6 back to List of values Value group Engine values Related FW 3 0 0 Resolution units 1 Bar Comm object 10268 Related applications All Description Internal value ...

Page 270: ...g CU Related FW 3 0 0 Resolution units 1 V Comm object 10603 Related applications All Description Engine alternator output voltage detected at D controller terminal D 6 back to List of values Value group Analog CU Related FW 3 0 0 Resolution units 1 Bar Comm object 9155 Related applications All Description Oil Press 6 back to List of values Value group Analog CU Related FW 3 0 0 Resolution units 1...

Page 271: ...he name Ain CU 4 is just default value which can be changed in analog input Property Name AIN CU 4 6 back to List of values Value group Analog CU Related FW 3 0 0 Resolution units 1 Comm object 9159 Related applications All Description Analog input value corresponding to analog input located directly on ID DCU controller Note The name Ain CU 5 is just default value which can be changed in analog i...

Page 272: ...he name Ain CU 7 is just default value which can be changed in analog input Property Name AIN CU 7 6 back to List of values Value group Analog CU Related FW 3 0 0 Resolution units 1 Comm object 9162 Related applications All Description Analog input value corresponding to analog input located directly on ID DCU controller Note The name Ain CU 8 is just default value which can be changed in analog i...

Page 273: ...Comm object 8235 Related applications All Description Controller binary inputs state indication ID BIN 6 back to List of values Value group Binary CU Related FW 3 0 0 Resolution units Comm object 8239 Related applications All Description Controller binary outputs state indication ID BOUT 6 back to List of values ...

Page 274: ...outpus LogBout 2 6 back to List of values Value group LogBout Related FW 3 0 0 Resolution units Comm object 9145 Related applications All Description List of logical binary outpus LogBout 3 6 back to List of values Value group LogBout Related FW 3 0 0 Resolution units Comm object 9146 Related applications All Description List of logical binary outpus LogBout 4 6 back to List of values Value group ...

Page 275: ... FW 3 0 0 Resolution units Comm object 9149 Related applications All Description List of logical binary outpus LogBout 7 6 back to List of values Value group LogBout Related FW 3 0 0 Resolution units Comm object 10627 Related applications All Description List of logical binary outpus which can be closed and opened remotely e g from InteliMonitor using the Remote switches tool or using MODBUS commu...

Page 276: ...st of values Value group Info Related FW 3 0 0 Resolution units Comm object 9090 Related applications All Description This value contains encrypted serial number of the controller and administrator password and is intended for retrieving of the lost password Send this number together with controller serial number to your distributor if you need to retrieve your password PasswordDecode 6 back to Li...

Page 277: ...iption This value contains actual controller mode The controller mode is selected by the setpoint Basic Settings Mode ID but the setpoint can be overridden by Logical Binary input Remote OFF Mode ID 6 back to List of values Value group Info Related FW 3 0 0 Resolution units 1 Comm object 10040 Related applications Description Code of the currently running system process timer The text representati...

Page 278: ...th a specific bit is defined in ESC Engine Specific Code and is not user configurable ECU Alarms 2 6 back to List of values Value group Info Related FW 3 0 0 Resolution units Comm object 10918 Related applications All Description States of predefined ECU alarms which are available with Modbus reading Note Alarm linked with a specific bit is defined in ESC Engine Specific Code and is not user confi...

Page 279: ...11678 Related applications All Description GPS coordinate received from InternetBridge NT IB NT Latitude 6 back to List of values Value group Info Related FW 3 0 0 Resolution units Comm object 11679 Related applications All Description GPS coordinate received from InternetBridge NT IB NT Longitude 6 back to List of values Value group Info Related FW 3 0 0 Resolution units 0 1 kts Comm object 12165...

Page 280: ... of values Value group Statistics Related FW 3 0 0 Resolution units 1 Comm object 10149 Related applications All Description Unsuccessful starts counter The counter is incremented always when Start fail alarm is issued Note The counter can be readjusted reset from InteliMonitor menu Monitor Set statistics NumUnscStarts 6 back to List of values Value group Statistics Related FW 3 0 0 Resolution uni...

Page 281: ... All Description Trip fuel consumption calculated by controller from LAI Fuel ConsAct TripCons 6 back to List of values Value group Statistics Related FW 3 0 0 Resolution units 1 Comm object 8230 Related applications All Description There are two Statistics registers Memo1 and Memo2 Those statistic values are based on Logical Analog Input Memory1 or Memory2 value in the time of Logical Binary inpu...

Page 282: ...2 value in the time of Logical Binary input Memo1 Trigger or Memo2 Trigger rising edge Both statistics values is possible to modify in InteliMonitor Set Statistics command Memo2 6 back to List of values Value group Statistics Related FW 3 0 0 Resolution units 0 1 nm Comm object 11321 Related applications All Description Momentary average fuel consumption per nautical mile It is available if both L...

Page 283: ...applications All Description Indicates the soot load of Diesel Particulate Filter in percent DPF Soot Load 6 back to List of values Value group Aftertreatment Related FW 3 0 0 Resolution units 1 Comm object 14522 Related applications All Description Indicates aftertreatment Diesel Exhaust Fluid tank level in percent DEF Level 6 back to List of values ...

Page 284: ...pwm not supported by ID DCU Marine 2 2 ECU J1939 4 virtual Format depends on ECU Analog outputs availability Analog output configuration It is possible to convert Source analog value by linear interpolation conversion The conversion is given by definition of two points Low and High one Following is example of transfer characteristics 0 100 to 0 20mA Following are examples of transfer characteristi...

Page 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...

Reviews: