InteliDrive DCU Marine - 3.0.0 Global Guide
31
Combined - Harbour mode (CMB archive)
ID-DCU MARINE can be switched to
EME
or
HRB
mode by ID-DCU MARINE Mode panel buttons.
EME mode behavior is like above.
In HRB mode the controller operates lik e in AUX mode (all engine protections are active) but message
“HARBOUR MODE” in Alarm list and Binary outputs HRB mode and binary output Common Alarm is active.
Controller starts and stops the engine according to the binary inputs Blackout Start or Remote Start, Rem
Start/Stop, Remote Stop or to the ID-DCU MARINE Start / Stop buttons. Binary inputs Blackout Start and
Remote Start and Remote Stop are inactive in LOC (Local) mode.
Propulsion mode (PRP archive)
PRP mode is designed for multiple propulsion engines with variable speed
Controller starts and stops the engine according to the binary inputs RemRepStart or Remote Start, Rem
Start/Stop, Remote Stop or to the ID-DCU MARINE Start / Stop buttons. Binary inputs RemRepStart and
Remote Start and Remote Stop are inactive in LOC (Local) mode.
All engine protections and all configured shutdown protections are active. Controller continuously monitors
all available engine parameters (oil pressure, water temperature, RPM, fuel level etc.). The engine will stop
and activates Common Warning and Common Shutdown outputs and writes record to the history file when
detects any active Shut down alarm. This condition can be signaled by Active call feature to remote operator
via modem, SMS or e-mail.
Other functions
Controller (except OFF mode) accepts when engine is started outside controller (by hand) or when controller
power supply is switched-on on already running engine.
3.1.4 Universal states
State is a value joined to each Analog input or value. State indicates if any protection configured on
corresponding analog input is active or not. When there is any state configured as protection the corresponding
Binary output appears in Analog protection list and can be used for selective external indication of the Alarm.
State is resetted (output is opened) when corresponding Alarm is not active and confirmed (Fault reset was
pressed).
There are seven universal (free) states available in ID-DCU MARINE-3.0.0 that are not joined to any value or
input.
Summary of Contents for InteliDrive DCU Marine
Page 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Page 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Page 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Page 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Page 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...