InteliDrive DCU Marine - 3.0.0 Global Guide
182
Related FW
3.0.0
Related applications
All
Comm object
158
Description
External “edge sensitive” request for engine start. Input is inactive in LOC (Local) mode. Adjustable number
of attempts (see setpoints
Engine params
: Crank Attempts, MaxCrank Time and Cranking Pause).
Remote Start
Blackout Start
RemRepStart
Panel START button
Input sensitive
Edge
sensitive;
2-nd edge
skips Idle
Edge sensitive;
Edge sensitive;
Edge sensitive;
2-nd edge skips Idle
Active in MODE
AUX; EME;
PRP
CMB:EME;
CMB:HRB
AUX; EME
CMB:EME;
CMB:HRB
(PRP not
available)
PRP
(other modes
not available)
AUX; EME; PRP
CMB:EME; CMB:HRB
LOC
Inactive in MODE
LOC
LOC
LOC
all time active
Number of starting
attempts
1 x
Engine params:
Crank Attempts
Engine
params:
Crank
Attempts
1 x
Engine starting signals
Remote Stop
Panel STOP button
(1 sec holding time for Stop button activation!)
Input sensitive
Edge sensitive;
2-nd edge skips Cooling
Edge sensitive;
2-nd edge skips Cooling
Active in MODE
AUX; EME; PRP
CMB:EME; CMB:HRB
AUX; EME; PRP
CMB:EME; CMB:HRB
Inactive in MODE
LOC
-
Engine stopping signals
Note:
The setpoint Crank Attempts is not followed if Sd Override is active, crank attempts number is
then unlimited in case of Blackout Start.
Blackout Start
Summary of Contents for InteliDrive DCU Marine
Page 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Page 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Page 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Page 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Page 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...