InteliDrive DCU Marine - 3.0.0 Global Guide
179
Related FW
3.0.0
Related applications
All
Comm object
152
Description
Binary input for Alarm acknowledge (level sensitive) has the same function as controller front panel button
Fault reset (i.e. the acknowledge function is screen sensitive).
Note:
There is separated acknowledge for ECU Alarms – see Binary input
Fault Reset
Related FW
3.0.0
Related applications
All
Comm object
153
Description
Binary input
Horn Reset
is level sensitive.
Horn Reset
Related FW
3.0.0
Related applications
All
Comm object
12
Description
Controller is switched to OFF mode if input is closed and back to previous mode after is opened. Input is not
active in LOC (Local) mode. Active binary input Remote OFF is indicated by “
L
” character in the right upper
corner on ID-DCU MARINE screen.
Note:
Remote OFF will switch controller to OFF mode even if the Access Lock or Remote Lock is active
or Controller mode is password protected.
Remote OFF
Related FW
3.0.0
Related applications
All
Comm object
14
Description
Controller is switched to
HRB
mode if closed and back to previous mode if opened. Input is not active in
LOC
(Local) mode.
Remote HRB
Related FW
3.0.0
Related applications
All
Comm object
161
Description
Binary output Close load is closed/opened depends on the state of Remote On/Off binary input when engine
RPM is over
Engine protection
: MinLoadSpeed. Remote On/Off is not active in LOC mode.
Remote On/Off
Summary of Contents for InteliDrive DCU Marine
Page 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Page 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Page 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Page 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Page 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...