InteliDrive DCU Marine - 3.0.0 Global Guide
146
Setpoint group
RPMdep Protect
Related FW
3.0.0
Range [units]
0.. 600 [s]
Default value
10
Step
1
Comm object
10150
Related applications
PRP
Config level
Standard
Setpoint visibility
Always
Description
RPM dependent Oil pressure protection delay. Corresponding protection is activated when Oil pressure is
below limit for OilPrRPMdel.
To activate RPM dependent oil pressure protection any analog value has to be linked with LAI: Oil Press.
Note:
RPM dependent oil pressure protection is fix configured Protection block type = Engine running
only with RunOnlyBlkDel1 delay.
OilPrRPMdel
Setpoint group
RPMdep Protect
Related FW
3.0.0
Range [units]
0,0 .. 10,0 [Bar]
Default value
0,0
YES
Step
0,1
Comm object
10144
Related applications
PRP
Config level
Standard
Setpoint visibility
Always
Description
Linear Warning characteristic is defined by two points for
Idle RPM
and
Nominal RPM
.
CPIdleRPMWrn
defines coolant pressure warning level at idle speed. For details see
description.
CPIdleRPMWrn
Summary of Contents for InteliDrive DCU Marine
Page 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Page 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Page 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Page 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Page 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...