InteliDrive DCU Marine - 3.0.0 Global Guide
148
Setpoint group
RPMdep Protect
Related FW
3.0.0
Range [units]
0 .. 600 [s]
Default value
10
Step
1
Comm object
10151
Related applications
PRP
Config level
Standard
Setpoint visibility
Always
Description
RPM dependent Coolant pressure protection delay. Corresponding protection is activated when Coolant
pressure is below limit for CoolPrRPMdel.
To activate RPM dependent coolant pressure protection any analog value has to be linked with LAI: Coolant
Press.
Note:
RPM dependent coolant pressure protection is fix configured Protection block type = Engine
running only with RunOnlyBlkDel1 delay.
CoolPrRPMdel