InteliDrive DCU Marine - 3.0.0 Global Guide
144
RPMdep protect (PRP only)
RPM dependent Oil pressure and Coolant pressure protections are available in PRP (propulsion) application
only. Both protections are by default set to Protection block type = RunOnlyBlkDel1 (Engine running - block
delay 1).
There are two setpoints for linear Warning limit, two for Shutdown limit and one for delay. Setpoints adjusting
step and range depends on corresponding sensor characteristics.
Note:
The particular RPM dependent protection is fully disabled if both xxxIdlexxx and xxxNomxxx parameters
are set to value 0,0. I.e. the protection is not activated even if measured value is negative (e.g. when there is a
wrong sensor calibration).
Setpoint group
RPMdep Protect
Related FW
3.0.0
Range [units]
0,0 .. 10,0 [Bar]
Default value
0,0
Step
0,1
Comm object
10140
Related applications
PRP
Config level
Standard
Setpoint visibility
Always
Description
Linear Warning characteristic is defined by two points for
Idle RPM
and
Nominal RPM
.OPIdleRPMWrn
defines oil pressure warning level at idle speed.
OPIdleRPMWrn
Summary of Contents for InteliDrive DCU Marine
Page 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Page 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Page 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Page 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Page 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...