InteliDrive DCU Marine - 3.0.0 Global Guide
134
Engine protect
Setpoint group
Engine protect
Related FW
3.0.0
Range [units]
0 .. 600 [s]
Default value
10
Step
1
Comm object
8264
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
The maximum time for which is the binary output Horn closed (horn, buzzer will sound). If it is requested to
sound hound until alarm is cleared, set the parameter to zero.
Horn Timeout
Setpoint group
Engine protect
Related FW
3.0.0
Range [units]
0 .. 60 [s]
Default value
10
Step
1
Comm object
10023
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
This parameter adjusts delay after engine start when alarms configured as RunOnlyBlkDel1 (i.e. "running
only", group #1) are started to be evaluated. The "running only" alarms are not beeing evaluated while the
engine is not running or then, after start, while the adjusted delay is running.
For details see drawing, which is part of
description.
RunOnlyBlkDel1