InteliDrive DCU Industrial 3.4.0 Global Guide
120
Setpoint group
Engine params
Related FW
3.4.0
Range [units]
1 .. 4000 [min]
Default value
1
Force value
Alternative config
Step
1
Comm object
8781
Related applications
AS, SS
Description
Time interval between prelubrication cycles –
.
Note:
To use Prelubrication, configure Binary output Prelubrication at first.
Prelubrication is disabled in controller OFF mode or when PrelubrTime is set to zero.
When engine is running Prelubrication binary output is opened.
Prelubrication starts PrelubrPause after engine stops. Prelubrication starts immediately when:
- controller power supply turns on
- mode changes from OFF to another
- Emergency Stop is released
PrelubrPause
Setpoint group
Engine params
Related FW
3.4.0
Range [units]
0 .. 600 [s]
Default value
60
Force value
Alternative config
Step
1
Comm object
9815
Related applications
AS, SS
Description
Under normal conditions the engine must certainly stop within this period. The period starts by issuing stop
command.
Stop Time
Setpoint group
Engine params
Related FW
3.4.0
Range [units]
0 .. 600 [s]
Default value
30
Force value
Alternative config
Step
1
Comm object
8258
Related applications
AS, SS
Description
Runtime of unloaded engine to cool down engine before stopping.
Cooling Time
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...