InteliDrive DCU Industrial 3.4.0 Global Guide
119
Setpoint group
Engine params
Related FW
3.4.0
Range [units]
0.0 .. 100.0 [%]
Default value
0,0
Force value
Alternative config
Step
0.1
Comm object
10010
Related applications
AS
Description
Offset of Idle speed in % of RPM difference between nominal and idle setpoints (Nominal RPM – Idle RPM)
–
see Function description details on page 63
Note:
100 % of
Engine Values: Requested Speed
is the range between
Engine params: Idle RPM
and
Basic setting: Nominal RPM
.
Idle Offset
Setpoint group
Engine params
Related FW
3.4.0
Range [units]
0 .. 600 [s]
Default value
10
Force value
Alternative config
Step
1
Comm object
9097
Related applications
AS, SS
Description
Idle time delay starts when RPM exceeds Starting RPM.
During the Idle time the
is opened and after then it is closed.
opens during Cooling period (Cooling Time) again.
Idle Time
Setpoint group
Engine params
Related FW
3.4.0
Range [units]
0 .. 600 [s]
Default value
0
Force value
Alternative config
Step
1
Comm object
8780
Related applications
AS, SS
Description
This is the time the binary output Prelubrication is active. The controller will activate binary output
Prelubrication for this amount of time, then pause for PrelubrPause, then activate again. This will continue
the entire time the engine is not running. Function is not active in controller OFF mode.
PrelubrTime
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...