InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
176
A
PPLICATION
V
OLTAGE GAIN AND
V
OLTAGE INT SETPOINTS ARE ACTIVE DURING
:
BTB
synchronization between “left” and “right” buses
N
OTE
:
See the chapter
Regulation loops overview
for general information about
regulation loops and their adjustment.
12.2.11 Group: Force value
12.2.11.1
Setpoint: Force value 1
Group
Force value
Range [units]
[-]
Related FW
3.0
Description
This is one of the 16 setpoints reserved for using as alternative setpoints for
the force value functions. The alternative setpoint is to be assigned to a
particular force value function and renamed in GenConfig.
See also the input
N
OTE
:
It is not obligatory to use one of these reserved setpoints for a force value
function. It is possible to use also any other setpoint or value with matching
dimension and decimal resolution.
N
OTE
:
There isn't any relation between the default names of the force value function
blocks, associated binary inputs and the default names of the reserved
setpoints. In other words, the setpoint with default name
Force value 3
is
not
related
to the
Force value 3
function block.
12.2.11.2
Setpoint: Force value 2
Group
Force value
Range [units]
[-]
Related FW
3.0