12.2.4 Group: ComProtSetting
12.2.4.1
Setpoint: Horn Timeout
Group
Engine Protect
Range [units]
OFF, 1s - 3600s, NO TIMEOUT [-]
Related FW
3.0
Force value
possible
YES
Description
This setpoint adjusts time after which the
deactivated although the alarms still haven't been reset. If the setpoint is
adjusted to OFF the horn output is not activated at all, the NO TIMEOUT
position means the horn output is not deactivated until the alarms are reset.
12.2.4.2
Setpoint: BinInp delay 1
Group
ComProtSetting
Range [units]
0.0 .. 600.0 [s]
Related FW
3.0
Description
This setpoint adjusts the delay #1 which can be assigned to an input
configured as alarm input (protection).
N
OTE
:
Protections configured at a binary inputs can have either fixed 0.5s
evaluation delay or there are three independent delay setpoints and one of
them can be assigned to each particular binary input protection.
12.2.4.3
Setpoint: BinInp delay 2
Group
ComProtSetting
Range [units]
0.0 .. 600.0 [s]
Related FW
3.0
Description
This setpoint adjusts the delay #2 which can be assigned to an input
configured as alarm input (protection).
N
OTE
:
Protections configured at a binary inputs can have either fixed 0.5s
evaluation delay or there are three independent delay setpoints and one of
them can be assigned to each particular binary input protection.