InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
123
12.2.3.3
Setpoint: Contr. address
Group
Comms settings
Range [units]
1 .. 32 [-]
Related FW
3.0
Description
This setpoint adjusts the address of the particular controller at the CAN2
and/or RS485 bus. Each gen-set connected to the same bus
must have
unique address
.
is in AUT position, the address is assigned
automatically. The setpoint
is preffered then, however if it is in
conflict with other controller present on the CAN2 bus other address will be
assigned to aviod address collision.
N
OTE
:
Address 1 is reccommended for standalone gen-sets.
N
OTE
:
If you are connecting to the controller remotely you have to adjust the proper
controller address in connection settings of the remote client (InteliMonitor,
GenConfig, Modbus client etc.)
N
OTE
:
Address of the controller is also used for Modbus communication via RS485
etc. Address adjusted by this setpoint is therefore universal address of the
controller.
12.2.3.4
Setpoint: RS232(1) mode
Group
Comms settings
Range [units]
DIRECT, MODEM (HW), MODEM (SW), MODBUS-DIRECT, MODBUS-
MDM(HW), ECU LINK [-]
Related FW
3.0
Description
This setpoint selects the connection type for the serial port COM1.
Available as RS232 in all controller types.
Available also as RS485 in the IG-NT if the external display bus is
not used. Selectable by the setpoint
IG-NT-BB, IG-NTC-BB, IS-NTC-BB and IS-NT - see
).
See the diagram of all related terminals in the chapter
Communication
.