controller even in the case of power supply failure. Physical unit of the output
statistic value has to correspond to the ratio unit “/X”.
N
OTE
:
Pulse width (both high/low levels) must be at least 100 ms in order to be
correctly sensed! Conversion ratio can be selected using the setpoints
ConvCoefPulse1/2/3/4. The converted values are visible in statistics
– values
PulseCounter 1/2/3/4. These values can be reset using Statistics window in
InteliMonitor.
12.2.3 Group: Comms settings
12.2.3.1
Setpoint: Controller name
Group
Comms settings
Range [units]
[-]
Related FW
3.0
Description
This setpoint is intended for a custom name of the controller, which is used
for identification of the controller in saved archives or remote connections.
Maximal length of the name is 15 characters.
The setpoint can't be modified via the IG-NT built-in terminal.
12.2.3.2
Setpoint: LB/UART Log
Group
Comms settings
Range [units]
DISABLED, ENABLED
Related FW
3.0
Force value
possible
YES
Description
The setpoint enables/disables logging of remote communication activity. If
logging is enabled connection and disconnection of each remote terminal as
well as entering access code are recorded into the history.
N
OTE
:
The terminal is disconnected automatically after 5 min of inactivity and next
communication request from the same terminal is considered as a new
connection. When logging is enabled in certain conditions the history may be
filled up with large number of records related to the communication and
important records may be overwritten quite fast.