IGS-NT-BC, SW Version 1.2.0,
©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
96
Setpoint: Bin selector 4
Group
Engine params
Range [units]
OFF, ON [-]
Related FW
3.0
Force value
possible
YES
Description
The setpoint is used to switch on and off the output
Setpoint: Horn Timeout
Group
Engine Protect
Range [units]
OFF, 1s - 3600s, NO TIMEOUT [-]
Related FW
3.0
Force value
possible
YES
Force value
possible
YES
Description
This setpoint adjusts time after which the
output is automatically deactivated
although the alarms still haven't been reset. If the setpoint is adjusted to OFF the
horn output is not activated at all, the NO TIMEOUT position means the horn
output is not deactivated until the alarms are reset.
Setpoint: BinInp delay 1
Group
Engine protect
Range [units]
0.0 .. 600.0 [s]
Related FW
3.0
Description
This setpoint adjusts the delay #1 which can be assigned to an input configured
as alarm input (protection).
N
OTE
:
Protections configured at a binary inputs can have either fixed 0.5s evaluation
delay or there are three independent delay setpoints and one of them can be
assigned to each particular binary input protection.
Setpoint: BinInp delay 2
Group
Engine protect
Range [units]
0.0 .. 600.0 [s]
Related FW
3.0
Description
This setpoint adjusts the delay #2 which can be assigned to an input configured
as alarm input (protection).