Binary output: Common BOC
Related FW
3.0
Description
The output is closed while there is at least one alarm of the
Breaker open&Cool-
down
type present in the alarm list. The alarm can be in any state, i.e. active
unconfirmed, active confirmed or inactive unconfirmed. See the chapter
Alarm
management
for more information.
Binary output: Common Al
Related FW
3.0
Description
The output is closed while there is at least one alarm of the
Alarm only
type
present in the alarm list. The alarm can be in any state, i.e. active unconfirmed,
active confirmed or inactive unconfirmed. See the chapter
Alarm management
for
more information.
Binary output: Common Hst
Related FW
3.0
Description
The output is closed for 1s when any alarm of
History record
type appears. See
the chapter
Alarm management
for more information.
Binary output: CommonActLev 1
Related FW
3.0
Description
The output is closed while there is at least one 1st level (yellow) alarm present in
the alarm list. The alarm can be in
any state
, i.e. active unconfirmed, active
confirmed or inactive unconfirmed. See the chapter
Alarm management
for more
information.
Binary output: CommonActLev 2
Related FW
3.0
Description
The output is closed while there is at least one 2nd level (red) alarm present in the
alarm list. The alarm can be in
any state
, i.e. active unconfirmed, active confirmed
or inactive unconfirmed.See the chapter
Alarm management
for more information.
Binary output: Alarm flashing
Related FW
3.0
Description
This is the flashing alternative of the output
, i.e. the output flashes with
period 1s/1s while the output