ID-FLX Lite & Telecom Global Guide
179
Setpoint group
Act. Calls/SMS
Related FW
2.5.0
Range [units]
OFF, ON [-]
Default value
-
Step
-
Comm object
8484
Related applications
Description
Set this setpoint to YES if you want to get messages when a red (shutdown) alarm occurs.
Note:
The target address (cellular network phone number or e-mail address) must be set correctly to the
setpoint(s) TelNo/Addr Ch1 resp.
Red Alarm Msg
Setpoint group
Act. Calls/SMS
Related FW
2.5.0
Range [units]
[-]
Default value
-
Step
-
Comm object
9597
Related applications
Description
Enter either a valid cellular network phone number or e-mail address to this setpoint, where the alarm
messages shall be sent. Type of active call is considered from the value of this parameter. If it consist „@“ it
is supposed to be e-mail address and active e-mail is sent. If the value is number, without „@“, it is
supposed to be the telephone number and active SMS is sent.
Note:
These setpoints can be modified from PC only!
For cellular network numbers use either national format (i.e. like number you will dial if you want to make
a local call) or full international format with "+" character followed by international prefix at the beginning.
TelNo/Addr Ch1, 2
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...