ID-FLX Lite & Telecom Global Guide
127
Setpoint group
Load limit
Related FW
2.5.0
Range [units]
CU:AI1, CU:AI2, CU:AI3, CU:AI4, CU:AI5, CU:AI6, CU:AI7, CU:AI8, CU:AI9,
AIO:IA1, AIO:AI2, AIO:AI3, AIO:AI4, RPM-BI3 [-]
Default value
CU:AI1
YES
Step
-
Comm object
11843
Related applications
Description
PI loop analog input selection. Source can be adjusted from controller analog inputs or from extension
module inputs. It is also possible to use Binary input 3 in function of RPM detection. The Speed request
(regulator output) is assigned to Reg Bias value in the case of selected analog input sensor fail.
Reg Input
Setpoint group
Load limit
Related FW
2.5.0
Range [units]
0 .. 10000 [-]
Default value
0
YES
Step
1
Comm object
11848
Related applications
Description
Constant PI regulator output when the LBI R Reg Disable = closed.
Reg Bias
Setpoint group
Load limit
Related FW
2.5.0
Range [units]
-10000 .. +10000 [-]
Default value
0
YES
Step
1
Comm object
11844
Related applications
Description
Regulator requested value.
Value of this Setpoint should be given in value of quantity without decimal point.
Example:
When AIN is configured in such way that Load limit set on 5 V to maintain the value
8.54 bar, then the value inserted to this Setpoint is 854.
Request 1
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...